CQM1-TC201 Omron, CQM1-TC201 Datasheet - Page 10

no-image

CQM1-TC201

Manufacturer Part Number
CQM1-TC201
Description
4 LOOP,THERMOCPLE IN, NPN OUT
Manufacturer
Omron
Datasheet

Specifications of CQM1-TC201

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
J SPECIFICATIONS
Temperature Controller Modules
Note: 1. Heater burnout detection will be disabled if the alarm is set to 0.0 A. The heater burnout alarm output will turn ON if the alarm is
Model
Input
Control mode
Setting and display
accuracy
Temperature adjustment
Proportional band
Derivative time
Integral time
Manual output
Control period
Input shift range
Sampling period
Output
External supply voltage
Internal current consumption
Heater
burn-
bu
out
alarm
p
2. If the control output is ON for less than 200 ms, heater burnout will not be detected and the heater current will not be measured.
Input type
Input sensor types
and set point ranges
Number of control
loops
Output refresh period
Output form
Maximum switching
capacity
Leakage current
Residual voltage
Maximum heater
current
Input current monitor-
ing accuracy
Heater burnout alarm
setting
Minimum ON time for
detection
set to 50.0 A.
CQM1-TC00j
Thermocouple input
K: 200 to 1,300°C
(--300 to 2,300°F)
J: 100 to 850°C
(--100 to 1,500°F)
Two (either 1 or 2 loops can be used)
ON/OFF or advanced PID control
°C Ranges
(Set point ±1% or
±3°C, whichever is
larger) ±1 digit max.
°F Ranges
(Set point ±1% or
±6°F, whichever is
larger) ±1 digit max.
0.8 °C/°F
40.0 °C/°F
240 s
40 s
20 s
1 s
1 s
NPN (TCj01) or PNP (TCj02) outputs with
short-circuit protection
100 mA, 24 VDC
0.3 mA max.
3.0 V max.
15 mA min.,
24 VDC
220 mA max. at 5 VDC
+10%
/--
15%
+10%
/--
15%
CQM1-TC10j
Platinum resistance
thermometer input
JPt: --99.9 to 450.0°C
(--99.9 to 800.0°F)
Pt: --99.9 to 450.0°C
(--99.9 to 800.0°F)
°C Ranges
(Set point ±1% or
±2°C, whichever is
larger) ±1 digit max.
°F Ranges
(Set point ±1% or
±4°F, whichever is
larger) ±1 digit max.
Programmable Controller
CQM1-TC20j
Thermocouple input
K, J, T, L, R, S, B
(See the following table
for temperature
ranges.)
4 loops (TCj01 or TCj02) or
2 loops with heater burnout alarm (TCj03 or
TCj04)
ON/OFF control, advanced PID control (2 degrees
of freedom), or manual operation
°C Ranges
(Set point ±0.3% or
±1°C, whichever is
larger) ±1 digit max.
°F Ranges
(Set point ±0.3% or
±2°F, whichever is
larger) ±1 digit max.
0.1 to 999.9 °C/°F (0.1°C/°F unit)
0.1 to 999.9 °C/°F (0.1°C/°F unit)
0 to 3,999 s (1 s unit)
0 to 3,999 s (1 s unit)
0.0% to 100.0% (0.1% unit)
1 to 99 s (1 s unit)
--99.9 to 999.9 °C/°F
0.5 s
0.5 s
NPN (TCj01/TCj03) or PNP (TCj02/TCj04)
outputs with short-circuit protection
100 mA, 24 VDC
0.1 mA max.
0.8 V max.
30 mA min.,
24 VDC
190 mA max. at 5 VDC
50 A, single-phase AC
±5% FS ±1 digit
0.1 to 49.9 A in 0.1 A increments (See Note 1)
200 ms (See Note 2)
(0.1°C/°F unit)
+10%
/--
CQM1H
15%
+10%
/--
15%
CQM1-TC30j
Platinum resistance
thermometer input
Pt, JPt
(See the following table
for temperature
ranges.)
0.1°C Ranges
(Set point ±0.3% or
±0.8 °C, whichever is
larger) ±1 digit max.
0.1°F Ranges
(Set point ±0.3% or
±1.6 °F, whichever is
larger) ±1 digit max.
(See note 1.)
0.01°C Ranges
(Set point ±0.3% or
±0.5 °C, whichever is
larger) ±1 digit max.
0.1 °C Ranges
(0.1°C/°F unit)
0.01 °C Ranges
(0.01°C/°F unit)
--99.9 to 999.9 °C/°F
--9.99 to 99.99 °C/°F
A--205

Related parts for CQM1-TC201