E5EK-TAA2 AC/DC24 Omron, E5EK-TAA2 AC/DC24 Datasheet - Page 6

no-image

E5EK-TAA2 AC/DC24

Manufacturer Part Number
E5EK-TAA2 AC/DC24
Description
Use AC100240 Models
Manufacturer
Omron
Series
E5EKr
Type
Digital Controller, Programmabler
Datasheet

Specifications of E5EK-TAA2 AC/DC24

Input Type
Current, Voltage, RTD, Thermocouple (Multiple)
Controller Type
On/Off
Temperature Range
Selectable, Varies By Input Type
Output Type
Output Units Available
Supply Voltage
24VAC/DC
Size
48mm W x 96mm H (1/8 DIN)
Features
Burnout Detection
Display Type
4 Digit (2), LEDs
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Communications
-
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
E5EK-TAA2AC/DC24
E5EKTAA2ACDC24
■ Output Unit Ratings and Characteristics
Note: An output relay (1 A at 250 VAC) is mounted on the position-proportional model. (When replacing, use the E53-R.)
■ Option Unit Ratings and Characteristics
Note: Event input is used for switching the target value, run or stop command, or automatic and manual mode with an external signal input.
■ Current Transformer Ratings
■ Heater Burnout Alarm
Note: 1. Use the K2CU-F@@A-@GS (with gate input terminals) for the detection of three-phase heater burnout.
E53-R
E53-S
E53-Q
E53-Q3
E53-Q4
E53-C3
E53-C3D
E53-V34
E53-V35
E53-AKB
E53-EN01
E53-EN02
E53-EN03
E53-AKF
Dielectric strength
Vibration resistance
Weight
Accessories (E54-CT3 only)
Max. heater current
Heater current value display accuracy
Heater burnout alarm setting range
Min. detection ON time
2. The heater burnout alarm is always OFF if the alarm is set to 0.0 A and always ON if the alarm is set to 50.0 A.
3. No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less than 190 ms.
Model
Relay output
SSR output
Voltage output
Linear current output
Linear voltage output
Event input
Communications
Transfer output
http://www.ia.omron.com/
Model
1,000 VAC (for 1 min)
50 Hz, 98 m/s
E54-CT1: approx. 11.5 g; E54-CT3: approx. 50 g
Armature: 2; Plug: 2
RS-232C
RS-422
RS-485
5 A at 250 VAC (resistive load)
1 A at 75 to 250 VAC (resistive load)
NPN: 40 mA at 12 VDC
NPN: 20 mA at 24 VDC
PNP: 20 mA at 24 VDC
4 to 20 mA, permissible load impedance: 600
0 to 20 mA, permissible load impedance: 600
0 to 10 VDC, permissible load impedance: 1 k min., resolution: approx. 2,600
0 to 5 VDC, permissible load impedance: 1 k
2
Contact input:
ON: 1 k max., OFF: 100 k
No-contact input:
ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.
Transmission method:
Synchronization method: Start-stop synchronization (asynchronous method)
Baud rate:
Transmission code:
4 to 20 mA:
Permissible load impedance: 600
Resolution: approx. 2,600
(10G)
Single-phase 50 A VAC (See note 1.)
0.1 to 49.9 A (in units of 0.1 A) (See note 2.)
190 ms (See note 3.)
5% FS 1 digit max.
(with short-circuit protection)
(with short-circuit protection)
(with short-circuit protection)
Half-duplex
1.2/2.4/4.8/9.6/19.2 kbps
ASCII
(c)Copyright OMRON Corporation 2007 All Rights Reserved.
min.
Specifications
Specifications
max.
min., resolution: approx. 2,600
max., resolution: approx. 2,600
max., resolution: approx. 2,600
E5EK
6

Related parts for E5EK-TAA2 AC/DC24