XCS-A502 TELEMECANIQUE, XCS-A502 Datasheet - Page 13

SAFETY SWITCH, 2NO/1NC

XCS-A502

Manufacturer Part Number
XCS-A502
Description
SAFETY SWITCH, 2NO/1NC
Manufacturer
TELEMECANIQUE
Datasheet

Specifications of XCS-A502

Contact Voltage Ac Max
250V
Contact Voltage Dc Max
24V
Contact Current Ac Max
6A
Contact Current Dc Max
540mA
Switch Terminals
Screw
Approval Bodies
EN1088, EN60204, EN60947-5-1
Conduit Thread Size
M20 X
2
Wiring to category 1 (EN 954-1)
Wiring examples with protection fuse to prevent shunting of the N/C contact, either by cable damage or by unauthorised tampering.
Locking on de-energisation
N/C + N/O + N/O
XCS-E53i i i i i 3
(1) Solenoid
(2) Auxiliary contact
E1-E2 : Solenoid supply
43-44 : Solenoid signalling contact
13-14 : Safety contact, available for redundancy
33-X1 : LED (orange) : actuator withdrawn
51-X1 : LED (green) : actuator inserted and locked
Note : these schemes are given as examples only, the designer must refer to EN 954-1 for guidance.
The risk assessment (EN 1050) will help the designer to determine the most appropriate risk reduction methods and the part played by the safety related
parts of the control system in reducing the risk.
2/26
References :
pages 2/18 to 2/21
Dimensions :
pages 2/23 and 2/24
(1)
F1
(2)
Te
X3
O
I
21
13
33
OG GN
X
X1
22
14
34
X
X2
Components for safety applications
Guard switches with solenoid interlocking
Metal, turret head, type XCS-E
Schemes
M
Locking on energisation
N/C + N/O + N/O
XCS-E55i i i i i 3
(1) Solenoid
(2) Auxiliary contact
E1-E2 : Solenoid supply
51-52 : Solenoid signalling contact
13-14 : Safety contact, available for redundancy
33-X1 : LED (orange) : actuator withdrawn
43-X1 : LED (green) : actuator inserted and locked
(1)
F1
(2)
X3
O
I
21
13
33
OG GN
X
X1
22
14
34
X
X2
M