K8AB-TH12S AC100-240 Omron, K8AB-TH12S AC100-240 Datasheet - Page 2

High Temp 0-1700 C Monitor Rel

K8AB-TH12S AC100-240

Manufacturer Part Number
K8AB-TH12S AC100-240
Description
High Temp 0-1700 C Monitor Rel
Manufacturer
Omron
Series
K8ABr
Type
Temperature Monitorr

Specifications of K8AB-TH12S AC100-240

Input Type
RTD, Thermocouple (Multiple)
Controller Type
On/Off
Temperature Range
Selectable, Varies By Input Type
Output Type
Relay
Supply Voltage
100 ~ 240VAC
Size
DIN Rail Module
Coil Voltage
100 VAC to 240 VAC
Contact Termination
Screw
Mounting Style
DIN Rail
Power Consumption
5 VA
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Features
-
Display Type
-
Communications
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
K8AB-TH12S-AC100-240
K8ABTH12SAC100240
Z2810
Specifications
■ Ratings
■ Characteristics
Item
Allowable voltage range
Power consumption
Sensor inputs
Output relay
External inputs
(for latch setting)
Setting method
Indicators
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
Setting accuracy
hysteresis width
Output relay
Sampling cycle
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Weight
Degree of protection
Memory protection
Safety
Standards
EMC
Terminal screw tightening torque
Crimp terminals
Case color
Case material
Mounting
Dimensions
Resistive load
Inductive load
Minimum load
Maximum contact voltage
Maximum contact current
Maximum switching capacity 1,500 VA
Mechanical life
Electrical life
Approved standards
EMC
Application standards
K8AB-TH11S
K8AB-TH12S
Contact input
Non-contact input
Power supply voltage
85% to 110% of power supply voltage
5 VA max.
Thermocouple: K, J, T, E; Platinum-resistance thermometer: Pt100
Thermocouple: K, J, T, E, B, R, S, PLII
One SPDT relay (3 A at 250 VAC, resistive load)
ON: 1 kΩ max., OFF: 100 kΩ min.
ON residual voltage: 1.5 V max., OFF leakage current: 0.1 mA max.
Leakage current: Approx. 10 mA
Rotary switch setting (set of three switches)
Power (PWR): Green LED, Relay output (ALM): Red LED
Alarm Mode (upper limit/lower limit), non-fail safe/fail safe selection, output latch, setting protection, temperature
unit °C/°F
−10 to 55°C (with no condensation or icing)
Relative humidity: 25% to 85%
−25 to 65°C (with no condensation or icing)
±2.0% of full scale
2°C
3 A at 250 VAC (cosφ = 1), 3 A at 30 VDC (L/R = 0 ms)
1 A at 250 VAC (cosφ = 0.4), 1 A at 30 VDC (L/R = 7 ms)
10 mA at 5 VDC
250 VAC
3 A AC
10,000,000 operations
Make: 50,000 times, Break: 30,000 times
500 ms
20 MΩ (at 500 V) between charged terminals and exposed uncharged parts
20 MΩ (at 500 V) between any charged terminals (i.e., between input, output, and power supply terminals)
20 MΩ (at 500 V) between contacts (open)
2,000 VAC 50/60 Hz for 1 min between charged terminals of different polarity
Vibration of 10 to 55 Hz and acceleration of 50 m/s
150 m/s
130 g
IP20
Non-volatile memory (number or writes: 200,000)
UL 61010-1, CSA C22.2 No. 1010-1, KOSHA
EN 61326
EN 61010-1 (pollution level 2, overvoltage category II)
EMI:
Radiation Interference Field Intensity: EN 55011 Group 1 Class A
Noise Terminal Voltage:
EMS:
Immunity ESD:
Immunity RF:
Immunity Burst:
Immunity Conducted Disturbance:
Immunity Surge:
Commercial Frequency
Immunity Magnetic Field:
Immunity Voltage Dip/Interrupting:
0.54 to 0.55 N·m
Two solid wires of 2.5 mm
Munsell 5Y8/1 (ivory)
ABS resin (self-extinguishing resin)
Mounted to DIN Track or with M4 screws
22.5 × 100 × 90 mm (W × D × H)
2
(100 m/s
100 to 240 VAC 50/60 Hz
2
for relay contacts) 3 times each in 6 directions in X, Y, and Z directions
2
or two ferrules of 1.5 mm
EN 61326
EN 55011 Group 1 Class A
EN 61326
EN 61000-4-2:
EN 61000-4-3:
EN 61000-4-4:
EN 61000-4-6:
EN 61000-4-5:
EN 61000-4-8:
EN 61000-4-11: 0.5 cycle, 100% (rated voltage)
2
for 5 min with 10 sweeps each in X, Y, and Z directions
2
with insulation sleeves can be tightened together.
2 W max. (24 VDC), 4 VA max. (24 VAC)
4 kV contact discharge (level 2)
8 kV air discharge (level 3)
(80 MHz to 1 GHz, 1.4 GHz to 2 GHz) (level 3)
2 kV power line (level 3)
2 kV output line (relay output) (level 4)
1 kV measurement line and I/O signal lines (level 4)
1 kV line-to-line: power line, output line
(relay output) (level 2)
2 kV line-to-ground: power line, output line
(relay output) (level 3)
30 A/m (50Hz) continuous time
10 V/m, amplitude-modulated
3 V (0.15 to 80 MHz) (level 3)
24 VAC 50/60 Hz or 24 VDC
K8AB-TH
2