TCT40-06E07K Triad Magnetics, TCT40-06E07K Datasheet

XFRMR CNTRL 24VAC 1.67A 12" LEAD

TCT40-06E07K

Manufacturer Part Number
TCT40-06E07K
Description
XFRMR CNTRL 24VAC 1.67A 12" LEAD
Manufacturer
Triad Magnetics
Type
Standardr
Datasheets

Specifications of TCT40-06E07K

Maximum Power
40 VA
Primary Winding(s)
Dual
Secondary Winding(s)
Single, No Center Tap
Series Output Voltage @ Current
24 VAC @ 1.67A
Mounting Type
Chassis Mount
Power Rating
40 VA
Dimensions
92.46 mm W x 56.38 mm H
Product
Control Transformers
Height
56.38 mm
Width
92.46 mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Parallel Output Voltage @ Current
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
237-1246

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
TCT40-06E07K
Manufacturer:
Triad Magnetics
Quantity:
135
TCT40-06E07K
Description:
Triad control transformers come with tamper resistant shrouds for safety and a
steel bracket welded to the bottom of the transformer for ease of mounting. These
transformers are design and have the safety agency recognition for application
where a Class 2 transformer is necessary. Some of the applications would include,
but not limited to HVAC, Control boards, Lighting, etc.
Electrical Specifications (@25C):
1. Maximum Power: 40VA
2. *Input (BLK-WHT): 120V, 50/60 Hz
3. Output (YEL-YEL): 24V @ 1.67Amps
4. Voltage Regulation: 15% TYP @ full load to no load
5. Temperature Rise: <40°C TYP
6. Hipot: 1500VAC – Input to Output, Input & Output to Core
7. Inherently Limited. No fusing required.
* Only one input voltage to be applied to primary at any time.
Construction:
Three flange bobbin construction with primaries and secondaries wound side by
side for low capacitive coupling. Unit weight is 1.5lbs.
Agency File:
UL: File E65390, UL 5085-3 (1585), Class 2 Transformer
cUL: File E65390, UL 5085-3 (1585) For Canadian Use (CSA 22.2, No.66.3-06)
Connections:
Input: 12±1” insulated leads, stripped and tinned 0.20±0.08”, 18AWG stranded
Output: 12±1” insulated leads, stripped and tinned 0.20±0.08”, 18AWG stranded
Schematic:
RoHS Compliance:
As of manufacturing date February 2005, all standard products meet the
requirements of 2002/95/EC, known as the RoHS initiative.
As of April 7, 2008, UL standards 506 and 1585 will be migrated to UL 5085-2 and
5085-3, respectively.
* Upon printing, this document is considered “uncontrolled”. Please contact
Web: www.TriadMagnetics.com
Phone 951-277-0757
Fax 951-277-2757
Triad Magnetics’ website for the most current version.
(BLK-RED): 240V, 50/60Hz
WHT
RED
BLK
22520B Temescal Canyon Road
Corona, California
92883
YEL
YEL
Control Transformer
Class 2
Publish Date: July 21, 2008
0.19+0.01,-0
1.80±.0.04
2.34±0.04
3.13±0.02
3.64±0.02
Picture for illustration only!!
0.87±0.04
2.6±0.02

Related parts for TCT40-06E07K