VPP24-2330 Triad Magnetics, VPP24-2330 Datasheet

TRANSF 12VAC 4.66A WORLD SERIES

VPP24-2330

Manufacturer Part Number
VPP24-2330
Description
TRANSF 12VAC 4.66A WORLD SERIES
Manufacturer
Triad Magnetics
Series
PC Mount: World Series™r
Type
Dual Primaryr
Datasheets

Specifications of VPP24-2330

Maximum Power
56 VA
Primary Winding(s)
Dual
Secondary Winding(s)
Dual, No Center Tap
Series Output Voltage @ Current
24 VAC @ 2.33A
Parallel Output Voltage @ Current
12 VAC @ 4.66A
Mounting Type
Through Hole
Power Rating
56 VA
Product
World Series Transformers
Brand/series
World Series™/VPP Series
Configuration
Bobbin
Current, Secondary
4.66/2.33 A
Dielectric Strength
4000 V (RMS)
Dimensions
3"W×1-13/16"H×2-1/2"D
Frequency
50/60 Hz
Number Of Outlets
2
Phase
1
Power, Rating
56 VA
Standards
UL, CSA, VDE
Temperature, Operating
+30 °C
Termination
Thru-Hole
Voltage, Primary
115/230 VAC
Voltage, Secondary
12/24 VAC
Weight
1.7 lbs.
Mounting Style
SMD/SMT
Height
1.812 in
Length
2.5 in
Termination Style
Solder
Width
3 in
Transformer Type
Power
Input Voltage
115V
Output Voltage
24V
Current Rating
4.66A
Transformer Mounting
PC Board
Secondary Current Nom
4.66A
Primary Voltages
115 / 230V
Rohs Compliant
Yes
Secondary Voltages
2 X 12V
Output Current
4.66A
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
10505
237-1092
VPP24–2330
Electrical Specifications (@25C)
1. Maximum Power: 56.0VA
2. Input: Series: 230VAC, 50/60Hz; Parallel: 115VAC, 50/60Hz
3. Output: Series
4. Voltage Regulation: 25% TYP @ full load to no load
5. Temperature Rise: 30C TYP (45C MAX allowed)
6. Insulation Resistance: 100MΩ
7. Hipot: 4000VAC between primary to secondary and windings to core.
8. Recommended Fuse
Construction:
Dual bobbin construction with an insulated shroud, both made of a high temperature material that exceeds
U
Safety:
Since the dual bobbin construction effectively reduces capacitance, electrostatic shielding is not required.
W
Agency File:
UL: File E53148, UL 5085-1 and 3 (formerly UL 506), General Purpose.
UL: File E65390, UL 5085-1 and 3 (formerly UL1585), Class 2/3.
CSA: File LR 37220. C22.2 NO. 66, General Purpose.
TUV: File R 72072385, EN 60950, (IEC950) information Technology Equipment.
A. Dimensions:
B. PIN DIM. : 0.045 SQ
C. WT Lbs. : 1.70
D. Mounting Holes: 0.180 dia. x 4
Connections
Input:
Output:
RoHS Compliance: Meets the requirements of 2002/95/EC, known as the RoHS initiative.
* Upon printing, this document is considered “uncontrolled”. Please contact Triad Magnetics’ website for
the most current version.
1
2
3
4
intended to be used independently.
Web: www.TriadMagnetics.com
Phone 951-277-0757
Fax 951-277-2757
Non-Inherently limited. Class 2 not wet, Class 3 wet.
Non-Inherently limited. Class 2.
Fuse must be used on secondary as conditions of acceptability for UL Class2/3 operation.
Primary and secondary windings are designed to be connected in series or parallel. Winding are not
L flammability requirements.
1.812
orld Series Transformers are designed and manufactured to meet the following agency approvals:
H
Series – Pin 7 to Pin 12, Jumper Pin 9 to Pin 10
Parallel – Pin 1 to Pin 6, Jumper Pin 1 to Pin 4 and Pin 3 to Pin 6
Parallel – Pin 7 to Pin 12, Jumper Pin 7 to Pin 10 and Pin 9 to Pin 12
Series – Pin 1 to Pin 6, Jumper Pin 4 to Pin 3
3.0
W
Series: Littelfuse p/n 313 2.5HXP, 2.5A 250V, slow blow, ¼ x 1 ¼ or,
Parallel: Littelfuse p/n 313 5.0HXP, 5A 250V, slow blow, ¼ x 1 ¼ or,
4
:
1
: 24.0V CT@ 2.33A; Parallel
2.50
Cooper Bussmann p/n BKMDL-2½, 2.5A 250V, ¼ x 1 ¼
Cooper Bussmann p/n BKMDL-5, 5A 250V, ¼ x 1 ¼
D
3
:
0.600
A
0.300
B
22520B Temescal Canyon Road
Corona, California
92883
1.900
2
: 12.0V @ 4.66A
C
ML
-
Units: In inches
MD
2.0
P
P C M
MW
2.5
O W E R
O U N T :
T
Publish Date: August 3, 2009
R A N S F O R M E R
W
O R L D
6
4
3
1
SCHEMATIC
S
E R I E S
12
10
9
7