H3CR-A-DC12 Omron, H3CR-A-DC12 Datasheet - Page 4

no-image

H3CR-A-DC12

Manufacturer Part Number
H3CR-A-DC12
Description
RELAY TIMER DPDT ANALOG 12VDC
Manufacturer
Omron
Series
H3CR-Ar
Datasheet

Specifications of H3CR-A-DC12

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
DPDT (2 Form C)
Delay Time
0.05 Sec ~ 300 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 240VAC
Voltage - Supply
12VDC
Mounting Type
Socket
Termination Style
11 Pin Socketable
Timing Adjustment Method
Hand Dial
Timing Initiate Method
Input Voltage
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
Z996
■ Time Ranges
Note: When the time setting knob is turned below “0” until the point where the time setting knob stops, the output will operate instantaneously at
Standard (0.05-s to 300-h) Models
Double (0.1-s to 600-h) Models
■ Ratings
Note: 1. DC ripple rate: 20% max. if the power supply incorporates a single-phase, full-wave rectifier.
Full scale
setting
Full scale
setting
Rated supply voltage (See notes 1, 2, and 5.) 100 to 240 VAC (50/60 Hz)/100 to 125 VDC, 24 to 48 VAC (50/60 Hz)/12 to 48 VDC (24 to 48 VAC/VDC for H3CR-
Operating voltage range
Power reset
Input
Power consumption
Control outputs
all time range settings.
2. Do not use an inverter output as the power supply. Refer to Safety Precautions for All Timers for details.
3. Models with 24-to-48-VAC or 12-to-48-VDC power supply have inrush current. Caution is thus required when turning ON and OFF power
4. The values are for when the terminals 2 and 7 and terminals 10 and 6 are short-circuited, and include the consumption current of the
5. Refer to Safety Precautions for All Timers when using the Timer together with a 2-wire AC proximity sensor.
Time unit
Time unit
to the Timer with a non-contact output from a device such as a sensor. (Models with an inrush current of approximately 50 mA and a 24-
VDC power supply are available (the H3CR-A-302 and H3CR-A8-302).)
input circuit.
1.2
3
12
30
2.4
6
24
60
0.05 to 1.2
0.3 to 3
1.2 to 12
3 to 30
0.1 to 2.4
0.6 to 6
2.4 to 24
6 to 60
s (sec)
s (sec)
A8E) (See note3.)
85% to 110% of rated supply voltage (90% to 110% at 12 VDC)
Minimum power-opening time: 0.1 s
No-voltage Input
ON impedance:
ON residual voltage:
OFF impedance:
Voltage Input
Max. permissible capacitance between inputs lines (terminals 6 and 7): 1,200 pF
Load connectable in parallel with inputs (terminals 6 and 7).
• 100 to 240 VAC/100 to 125 VDC
• 24 to 48 VAC/12 to 48 VDC
H3CR-A/-A8
• 100 to 240 VAC/100 to 125 VDC
• 24 to 48 VAC/12 to 48 VDC
H3CR-AP (See note 3)
• 100 to 240 VAC/100 to 125 VDC
• 24 to 48 VAC/12 to 48 VDC
H3CR-A8E
• 100 to 240 VAC/100 to 125 VDC
• 24 to 48 VAC/VDC
H3CR-AS/-A8S
• 24 to 48 VAC/12 to 48 VDC
Time limit contacts:
Transistor output:
Instantaneous contact: 5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cosφ = 1)
High (logic) level:
Low (logic) level:
High (logic) level:
Low (logic) level:
(When at 240 VAC, 60 Hz)
(When at 24 VDC)
(When at 240 VAC, 60 Hz)
(When at 24 VDC)
(When at 240 VAC, 60 Hz)
(When at 24 VDC)
(When at 24 VDC)
Relay ON: approx. 2.0 VA (1.6 W)
Relay ON: approx. 0.8 W
Relay ON: approx. 2.5 VA (2.2 W) (See note 4.) Relay OFF: approx. 1.8 VA (1.7 W) (See note 4.)
Relay ON: approx. 0.9 W (See note 4.)
Relay ON/OFF: approx. 2 VA (0.9 W)
Relay ON/OFF: approx. 0.9 W
Output ON: 0.3 W Output OFF: 0.2 W
0.12 to 1.2
0.24 to 2.4
85 to 264 VAC/85 to 137.5 VDC
0 to 10 VAC/0 to 10 VDC
20.4 to 52.8 VAC/10.8 to 52.8 VDC
0 to 2.4 VAC/0 to 1.2 VDC
5 A at 250 VAC/30 VDC, 0.15 A at 125 VDC, resistive load (cosφ = 1)
Open collector (NPN/PNP), 100 mA max. at 30 VDC max.,
residual voltage: 2 V max.
1 kΩ max.
1 V max.
100 kΩ min.
min (min)
min (min)
h (hrs)
h (hrs)
Relay OFF: approx. 1.3 VA (1.1 W)
Relay OFF: approx. 0.2 W
Relay OFF: approx. 0.3 W (See note 4.)
1.2 to 12
3 to 30
12 to 120
30 to 300
2.4 to 24
6 to 60
24 to 240
60 to 600
×10 h (10 hrs)
×10 h (10 hrs)
H3CR-A
4

Related parts for H3CR-A-DC12