H3CR-A8E AC100-240/DC100-125 Omron, H3CR-A8E AC100-240/DC100-125 Datasheet - Page 19

RELAY ANALOG SET DPDT 8PIN

H3CR-A8E AC100-240/DC100-125

Manufacturer Part Number
H3CR-A8E AC100-240/DC100-125
Description
RELAY ANALOG SET DPDT 8PIN
Manufacturer
Omron
Series
H3CR-Ar

Specifications of H3CR-A8E AC100-240/DC100-125

Mounting Type
Socket
Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
DPDT (2 Form C)
Delay Time
0.05 Sec ~ 300 Hrs
Output Type
Mechanical Relay
Contact Rating @ Voltage
5A @ 250VAC
Voltage - Supply
100 ~ 240VAC, 100 ~ 125VDC
Termination Style
8 Pin Socketable
Timing Adjustment Method
Hand Dial
Timing Initiate Method
Input Voltage
Timing Range
0.05 s to 300 Hrs
Supply Voltage
100 VAC to 240 VAC, 100 VDC to 125 VDC
Accuracy
+/- 0.2 %
Current Rating (max)
5 A
Display Type
Hand Dial
Operating Temperature Range
- 10 C to + 55 C
Time Range
0.05 Sec. To 300 Hr.
Supply Voltage Ac, Min
100VAC
No. Of Timing Functions
4
Body Material
94B3297
No. Of Pins
8
Supply Voltage Ac, Max
240VAC
Load Current Rms Max
5A
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
H3CR-A8EAC100-240/DC100-125
H3CRA8EAC100240DC100125
H3CRA8EAC100240DC100125
Q3619148
Safety Precautions (H3CR-A)
Refer to Safety Precautions for All Timers.
Note: The following precautions apply to all H3CR-A models.
■ Power Supplies
For the power supply of an input device of the H3CR-A@/-A@S/-AP,
use an isolating transformer with the primary and secondary
windings mutually isolated and the secondary winding not grounded.
The H3CR-A@/-A@S/AP’s power supply terminal 2 is a common ter-
minal for input signals to the Timer. Do not disconnect the wires on
terminal 2, otherwise the internal circuitry of the Timer will be dam-
aged.
Make sure that the voltage is applied within the specified range, oth-
erwise the internal elements of the Timer may be damaged.
Correct
Incorrect
G,
5, 6, 7
S,
G,
Input terminal
Input device
5, 6, 7
R
2
S,
5, 6, 7
G, S, R
Input device
R
2
Input
terminal
H3CR-A
H3CR-A
terminal
Input
transformer
Isolation
10
H3CR-A
2
Isolation transformer is required.
10
2
2
10
Power supply
Power
supply
■ Input/Output
Relationship between Input and Power
Supply Circuits (except for H3CR-A8E)
The H3CR-A (except for H3CR-A8E) uses transformerless power
supply. When connecting a relay or transistor as an external signal
input device, pay attention to the following points to prevent short-
circuiting due to a sneak current to the transformerless power supply.
If a relay or transistor is connected to two or more Timers, the input
terminals of those Timers must be wired properly so that they will not
differ in phase, otherwise the terminals will be short-circuited to one
another.
It is impossible to provide two independent power switches as shown
below regardless of whether or not the Timers are different in phase.
Incorrect
Correct
Contact or transistor for
external input signal
Input
terminal
Input
terminal
Input
terminal
Input
terminal
Input
terminal
Input
terminal
H3CR-A
Short-circuit current
Power supply
H3CR-A
Power supply
Power supply
19