H3YN-4 AC100-120 Omron, H3YN-4 AC100-120 Datasheet - Page 4

RELAY TIMER ANALOG 4PDT 0-10MIN

H3YN-4 AC100-120

Manufacturer Part Number
H3YN-4 AC100-120
Description
RELAY TIMER ANALOG 4PDT 0-10MIN
Manufacturer
Omron
Series
H3YNr
Datasheets

Specifications of H3YN-4 AC100-120

Relay Type
Integrated
Function
Programmable (Multi-Function)
Circuit
4PDT (4 Form C)
Delay Time
0.1 Sec ~ 10 Min
Output Type
Mechanical Relay
Contact Rating @ Voltage
3A @ 250VAC
Voltage - Supply
100 ~ 120VAC
Mounting Type
Socket
Termination Style
Socketable
Timing Adjustment Method
Hand Dial
Timing Initiate Method
Input Voltage
Timing Range
0.1 s to 10 min
Supply Voltage
100 V to 120 V
Current Rating (max)
3 A
Product
Analog Timer
Contact Configuration
4PDT
Nom Input Voltage
120VAC
Delay Time Range
0.1s To 10min
Timing Adjustment
DIP Switch
Relay Mounting
Plug In
Supply Voltage Max
120VAC
No. Of Poles
4
Contact Carrying Power
14VA
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Contains lead / RoHS compliant by exemption
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Contains lead / RoHS compliant by exemption
Other names
H3YN-4 AC100-240
H3YN4AC100120
H3YN4AC100240
Z1136
■ Life-test Curve (Reference Value)
H3YN-2/-21
H3YN-4/-41
H3YN-4-Z/-41-Z
5,000
1,000
5,000
1,000
5,000
1,000
500
200
500
200
500
100
60
24 VDC,
resistive load
Reference: A maximum current of 0.6 A can be switched at 125 VDC (cosφ = 1).
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cosφ = 1).
Reference: A maximum current of 0.5 A can be switched at 125 VDC (cosφ = 1).
Load current (A)
Load current (A)
Load current (A)
250 VAC, resistive load
250 VAC, cosφ = 1
24 VDC, cosφ = 1
250 VAC, cosφ = 1
24 VDC, cosφ = 1
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases,
a life of 100,000 operations can be expected.
The minimum applicable load is 1 mA at 5 VDC (P reference value).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases,
a life of 100,000 operations can be expected.
The minimum applicable load is 1 mA at 1 VDC (P reference value).
Maximum current of 0.2 A can be switched if L/R is 7 ms. In both cases,
a life of 100,000 operations can be expected.
The minimum applicable load is 0.1 mA at 1 VDC (P reference value).
5,000
1,000
5,000
1,000
500
200
500
200
Load current (A)
Load current (A)
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
250 VAC, cosφ = 0.4
24 VDC, L/R = 7 ms
H3YN
4

Related parts for H3YN-4 AC100-120