G3NA-225B DC5-24 Omron, G3NA-225B DC5-24 Datasheet - Page 5

RELAY SSR 120VAC@25A ZERO DC IN

G3NA-225B DC5-24

Manufacturer Part Number
G3NA-225B DC5-24
Description
RELAY SSR 120VAC@25A ZERO DC IN
Manufacturer
Omron
Series
G3NAr

Specifications of G3NA-225B DC5-24

Load Current
25A
Circuit
SPST-NO (1 Form A)
Output Type
AC, Zero Cross
Voltage - Input
5 ~ 24VDC
Voltage - Load
19 ~ 264 V
Mounting Type
Chassis Mount
Termination Style
Screw Terminal
Package / Case
Hockey Puck
Control Voltage Range
5VDC To 24VDC
Operating Voltage Range
19VAC To 264VAC
Isolation Voltage
2500VAC
Control Voltage Type
DC
Relay Terminals
Screw
Load Voltage Max
240VAC
Load Voltage Min
24VAC
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
On-state Resistance
-
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
G3NA-225B-DC5-24
G3NA225BDC524
Z921
G3NA
160
Inrush Current Resistivity
Non-repetitive (Keep the inrush current to half the rated value if it occurs repetitively.)
G3NA-205B
Heat Sink Size vs. Load Current
G3NA-220B
G3NA-240B/440B/450B
Ambient temperature
80 C
Energizing time (ms)
Energizing time (ms)
Load current (A)
Ambient temperature
40 C
Aluminum plate
3.2 mm thick
G3NA-210B/410B
G3NA-D210B
Note: The heat sink size refers to the combined area of the sides of the heat
Energizing time (ms)
Energizing time (ms)
sink that radiate heat. For example, when a current of 18 A is allowed
to flow through the SSR at 40 C, the graph shows that the heat sink
size is about 450 cm
the heat sink must be 15 cm (15
2
. Therefore, if the heat sink is square, one side of
2
G3NA-220B/420B
Temperature Characteristics
(with Must Operate Voltage
and Must Release Voltage)
G3NA-2jjB AC Input
x 2 = 450) or longer.
Energizing time (ms)
Ambient temperature ( C)
G3NA

Related parts for G3NA-225B DC5-24