P2CF-11-E Omron, P2CF-11-E Datasheet - Page 22

no-image

P2CF-11-E

Manufacturer Part Number
P2CF-11-E
Description
SOCKET 11-PIN FOR H3CR-H
Manufacturer
Omron
Type
Socketr
Series
-r
Datasheets

Specifications of P2CF-11-E

Number Of Positions
11
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Features
-
Socket Mounting
DIN Rail
Socket Terminals
Screw
Voltage Rating
240VAC
No. Of Pins
11
Accessory Type
Finger Safe Terminal
Rohs Compliant
Yes
For Use With/related Products
Multiple Series
For Use With
Z2998 - RELAY TIMER DGTL SPDT 100/240VACZ2366 - RELAY REPEAT CYCLE ANLG 30HRSZ997 - RELAY TIMER ANALOG 24VDC/ACZ2358 - RELAY REPEAT CYCLE ANLG 30HRSZ876 - RELAY TIMER DPDT ANALOG 120\240V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
P2CF11E
22
E5AN/E5EN
Specifications
Ratings
✽ A 2-level display when shipped from the factory. A 3-level display is activated if parameters are initialized. For details on the third display level,
Power supply voltage
Operating voltage range
Power
consumption
Sensor input
Input impedance
Control method
Control
output
Auxiliary
output
Event
input
External power supply for ES1B 12 VDC 10%, 20 mA, short-circuit protection circuit provided
Setting method
Indication method
Multi SP
Bank switching
Other functions
Ambient operating temperature
Ambient operating humidity
Storage temperature
refer to the User’s Manual, Basic Type (Cat. No. H156).
Relay output
Voltage output
(for driving SSR)
Current output
Long-life relay out-
put
Number of outputs
Output specifica-
tions
Number of inputs
External contact in-
put specifications
No D in model number: 100 to 240 VAC, 50/60 Hz
D in model number: 24 VAC, 50/60 Hz; 24 VDC
85% to 110% of rated supply voltage
100 to 240 VAC: 10 VA
24 VAC/VDC: 5.5 VA (24 VAC)/4 W (24 VDC)
Models with temperature inputs
Models with analog inputs
Current input: 150
ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5 V,
10 mA
Output voltage: 12 VDC 15% (PNP), max. load current: 40 mA,
With short-circuit protection circuit: Max. load current of 21 mA for control output 2
4 to 20 mA DC/0 to 20 mA DC, load: 600
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 1,000,000 operations, load power supply voltage: 75
to 250 VAC (DC loads cannot be connected.), minimum applicable load: 5 V, 10 mA, leakage current: 5 mA
max. (250 VAC, 60 Hz)
3
Relay output: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable
load: 5 V, 10 mA
2
Contact input: ON: 1 k
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
Current flow: Approx. 7 mA per contact
Digital setting using front panel keys
11-segment digital display and individual indicators (7-segments displays also possible)
Character height: E5AN: PV: 15.8 mm, SV: 9.5 mm, MV: 6.8 mm; E5EN: PV: 11.8 mm, SV: 8.1 mm,
Content of 3-level display: PV/SV/MV, PV/SV/multi-SP, or soak time remain ✽
Number of digits: 4 for PV, SV, and MV
Up to four set points (SP0 to SP3) can be saved and selected using event inputs, key operations, or serial
communications.
Not supported.
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burnout
detection, 40% AT, 100% AT, MV limiter, input digital filter, self-tuning, temperature input shift, run/stop,
protection functions, control output ON/OFF counter, extraction of square root, MV change rate limit, logic
operations, PV/SV status display, simple program, automatic cooling coefficient adjustment
25% to 85%
10 to 55 C (with no condensation or icing), for 3-year warranty: 10 to 50 C
25 to 65 C (with no condensation or icing)
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Infrared temperature sensor: 10 to 70 C, 60 to 120 C, 115 to 165 C, or 140 to 260 C
Voltage input: 0 to 50 mV
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
MV: 5.8 mm
max., Voltage input: 1 M
max., OFF: 100 k
max., resolution: approx. 10,000
min.
min. (Use a 1:1 connection when connecting the ES2-HB.)

Related parts for P2CF-11-E