2966207 Phoenix Contact, 2966207 Datasheet - Page 2

PLC RELAY SPDT 230AC/DC

2966207

Manufacturer Part Number
2966207
Description
PLC RELAY SPDT 230AC/DC
Manufacturer
Phoenix Contact
Series
-r
Datasheets

Specifications of 2966207

Relay Type
General Purpose
Contact Form
SPDT (1 Form C)
Contact Rating (current)
6A
Switching Voltage
250VAC
Coil Type
Standard
Coil Current
3.2mA
Coil Voltage
230VAC/DC
Mounting Type
DIN Rail
Termination Style
Screw Terminal
Circuit
SPDT (1 Form C)
Contact Rating @ Voltage
6A @ 250VAC
Contact Rating
6 A at 250 V
Contact Material
Silver Tin Oxide
Brand/series
PLC-RSC/RSP
Function
PLC
Phoenix Part Number
PLC-RSC-230UC/21
Turn On Voltage (max)
-
Turn Off Voltage (min)
-
Features
LED Indicator, PLC Terminal Block
Operate Time
7ms
Release Time
15ms
Coil Power
-
Coil Resistance
-
Operating Temperature
-25°C ~ 55°C
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Control On Voltage (max)
-
Control Off Voltage (min)
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
PLC-RSC-230UC/21
PLC-RSC-230UC/21
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2966207
PHOENIX CONTACT Deutschland GmbH
http://www.phoenixcontact.de
Nominal input current at U
Typical response time
Typical release time
Operating voltage display
Name of protection
Protective circuit/component
Contact side
Contact type
Contact material
Maximum switching voltage
Minimum switching voltage
Maximum inrush current
Min. switching current
Limiting continuous current
Interrupting rating (ohmic load) max.
General data
Width
Height
Depth
Test voltage relay winding/relay contact
Ambient temperature (operation)
Ambient temperature (storage/transport)
Operating mode
Service life mechanical
Inflammability class in acc. with UL 94 (housing)
Standard designation
IN
Order No.: 2966207
3.2 mA (at U
3 mA (at U
7 ms
15 ms
Yes
Bridge rectifier
Bridge rectifier
Single contact, 1-PDT
AgSnO
250 V AC/DC (The separating plate PLC-ATP should be installed
for voltages larger than 250 V (L1, L2, L3) between identical
terminal blocks in adjacent modules. Potential bridging is then
carried out with FBST 8-PLC... or ...FBST 500...)
12 V AC/DC
(on request)
10 mA
6 A
140 W (for 24 V DC)
20 W (for 48 V DC)
18 W (for 60 V DC)
23 W (for 110 V DC)
40 W (for 220 V DC)
1500 VA (for 250 V AC)
6.2 mm
94 mm
80 mm
4 kV AC (50 Hz, 1 min)
-25 °C ... 55 °C
-40 °C ... 85 °C
100% operating factor
2 x 10
V0
Standards/regulations
7
cycles
N
= 220 V DC)
N
= 230 V AC)
Mar 24, 2010
Page 2 / 7

Related parts for 2966207