P40C42D12C1-24 Tyco Electronics, P40C42D12C1-24 Datasheet - Page 2

CONTACTOR 24VDC 40A MAG 3PST

P40C42D12C1-24

Manufacturer Part Number
P40C42D12C1-24
Description
CONTACTOR 24VDC 40A MAG 3PST
Manufacturer
Tyco Electronics
Series
P40r
Datasheet

Specifications of P40C42D12C1-24

Relay Type
Contactor
Contact Form
3PST-NO-DM (3 Form X)
Contact Rating (current)
40A
Switching Voltage
600VAC
Coil Type
Standard
Coil Current
286mA
Coil Voltage
24VDC
Turn On Voltage (max)
18 VDC
Mounting Type
Chassis Mount
Termination Style
Screw Terminal, .250" QC
Circuit
3PST-NO-DM (3 Form X)
Contact Rating @ Voltage
40A @ 600VAC
Control On Voltage (max)
18 VDC
No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
Bracket
Coil Voltage Vdc Nom
24V
Relay Terminals
Screw Clamp
Nom Operating Power
7.5W
Contact Voltage Ac Nom
600V
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Control Off Voltage (min)
-
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
1423254-7
824
Ordering Information
Our authorized distributors are more likely to maintain the following items in stock for immediate delivery.
P30P42A12P1-120
P30P42D12P1-24
P30P47A12P1-120
P30P47D12P1-24
Dimensions are shown for
reference purposes only.
1. Type:
2. Auxiliary Switch:
3. Main Contact Arrangement:
4. Coil Control Input:
5. Mounting and Installed Accessories:
6. Main Contact Terminals:
7. Auxiliary Contact Terminals:
8. Coil Terminals:
9. Coil Voltage:
P30 = Definite Purpose Contactor, 30 amp.
P40 = Definite Purpose Contactor, 40 amp.
P = No Aux. Switch
C = 1 Form C (SPDT)
42 =
43 =
45 =
A = Alternating Current, 50/60 Hz.
1 = Standard Mounting
2 = Screw Terminals
3 = Screw Terminals & Dual .250” (6.35mm) Quick Connect
4 = Box Lug
P = No Auxiliary Switch
C = .187” (4.75mm) Quick Connect
1 = Combination 8-32* Screw Terminal and .250” (6.35mm) Quick Connect
24, 120, 240 or 277VAC
12, 24 or 120VDC
3 Form X (3PST-NO-DM)
2 Form X (DPST-NO-DM)
& 1 Form Y (SPST-NC-DB)
1 Form X (SPST-NO-DB)
& 2 Form Y (DPST-NC-DB)
P40P42A12P1-24
P40P42A12P1-120
P40P42A12P1-240
P40P42D12P1-24
Typical Part No.
F = 2 Form C (DPDT)
47 = 4 Form X (4PST-NO-DM)
48 = 2 Form X (DPST-NO-DM)
49 = 4 Form Y (4PST-NC-DB)
Other contact arrangements are available.
D = Direct Current
Dimensions are in inches over
(millimeters) unless otherwise
specified.
& 2 Form Y (DPST-NC-DB)
B
P30
Issued 3-03 (PDF Rev. 5-05)
5 = Captive Pressure Plate
6 = Box Lug & Dual .250” (6.35mm) Quick Connect
Catalog 1308242
P
Specifications and availability
subject to change.
42
A
1
4
P
www.tycoelectronics.com
Technical support:
Refer to inside back cover.
1
-240
P&B

Related parts for P40C42D12C1-24