SF4D-DC24V Panasonic Electric Works, SF4D-DC24V Datasheet - Page 5

RELAY SAFETY 6A 24VDC PCMNT 8PST

SF4D-DC24V

Manufacturer Part Number
SF4D-DC24V
Description
RELAY SAFETY 6A 24VDC PCMNT 8PST
Manufacturer
Panasonic Electric Works
Series
SFr
Type
Safety Relayr
Datasheets

Specifications of SF4D-DC24V

Relay Type
Safety
Contact Form
8PST (4 Form A, 4 Form B)
Contact Rating (current)
6A
Switching Voltage
250VAC
Coil Type
Standard
Coil Current
20.8mA
Coil Voltage
24VDC
Turn On Voltage (max)
14.4 VDC
Turn Off Voltage (min)
3.6 VDC
Mounting Type
Through Hole
Termination Style
PC Pin
Circuit
8PST (4 Form A, 4 Form B)
Contact Rating @ Voltage
6A @ 250VAC
Control On Voltage (max)
14.4 VDC
Control Off Voltage (min)
3.6 VDC
Brand/series
SF Series
Current, Rating
6 A
Function
Safety
Material, Contact
Gold-Flashed Silver Alloy
Number Of Pins
18
Resistance, Coil
1.152 Ohms
Standards
cULus, TUV, CSA
Temperature, Operating
-40 to +70 °C
Termination
Solder
Voltage, Breakdown
2500 V (RMS) (Between Contacts and Coil)
Voltage, Control
24 VDC
Voltage, Rating
380 VAC
Weight
1.66 Oz. (Approx.)
Relay Construction
Non-Latching
Contact Arrangement
4PST-NO/4PST-NC
Coil Voltage Dc
24V
Voltage Rating (vdc)
30V
Voltage Rating (vac)
440V
Dropout Volt (min)
3.6VDCV
Coil Resistance
1.152kohm
Pick-up Voltage (max)
18VDC
Maximum Power Rating
180W/1.5KVA
Operate Time
30ms
Contact Current Rating
6A
Contact Material
Silver Tin Oxide/Gold Flash
Coil Suppression Diode
No
Push To Test Button
No
Led Indicator
No
Seal
Unsealed
Product Height (mm)
16.5mm
Product Depth (mm)
33mm
Product Length (mm)
53.3mm
Operating Temp Range
-40C to 70C
Pin Count
18
Mounting Style
Through Hole
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
255-1441

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Company:
Part Number:
SF4D-DC24V
Quantity:
29
SF Double contact type
THE OPERATION OF SF RELAYS (when contacts are welded)
SF relays work to maintain a normal operating state even when the contact welding occur by overloading or short-circuit
currents. It is easy to make weld detection circuits and safety circuits in the design to ensure safety even if contacts weld.
1) 2 Form A 2 Form B type
If the form “b” contact (No. 1 and 3) welds, the armature becomes non-operational, the contact gaps at the three form “a” contacts are
maintained at greater than 0.5 mm
When the form “a” contacts (No. 2 or 4) weld, the armature remains in a non-returned state and the contact gap at the two form “b”
contact is maintained at greater than 0.5 mm
No.4
No.3
No.4
No.3
No.4
No.3
Terminal No.
Contact No.
Contact Operation Table
Form “b” Contact Weld
Form “a” Contact Weld
Non-energized
11–12
No.1
Energized
No.2
7–8
No.3
5–6
9–10
No.4
No.1
No.2
No.1
No.2
No.1
No.2
.020
All Rights Reserved © COPYRIGHT Panasonic Electric Works Co., Ltd.
inch. Reliable isolation is thus ensured.
.020
The table below shows the state of the other contacts when the current through
the welded form “a” contact is 0 V and the rated voltage is applied through the
form “b” contact.
* Contact gaps are shown at the initial state.
If the contacts change state owing to loading/breaking
it is necessary to check the actual loading.
terminal
Welded
No.4
No.3
No.4
No.3
Non-energized (when No. 2 contact is welded)
No.
Energized (when No. 1 contact is welded)
inch. Reliable isolation is thus ensured.
1
2
3
4
>0.5
>0.5
1
State of other contacts
>0.5
>0.5
2
>0.5
>0.5
3
No.1
No.2
No.1
No.2
>0.5
>0.5
4
Example: If the No. 1 contact welds
Each of the three form “a” contacts (No. 2 and 4)
maintain a gap of greater than 0.5 mm
Example: If the No. 2 contact welds.
The two form “b” contact (No. 1 or 3) maintains a gap of
greater than 0.5 mm
>0.5: contact gap is kept at
Empty cells: either closed or open
min. 0.5 mm
.020
.020 inch
inch.
.020
inch.

Related parts for SF4D-DC24V