Description
FAN REPLACEMENT FOR S82J/S8PS
Manufacturer
Omron
Series
S82Jr
Datasheets

Specifications of S82Y-JFAN

Accessory Type
Fan
For Use With/related Products
S82J 600W Power Supplies
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
S82YJFAN
■ Overload Protection
10- to 300-W Models
The Power Supply is provided with an overload protection function
that protects the Power Supply from possible damage by overcurrent.
When the output current rises above 105% to 160% of the rated
output current, the protection function is triggered, automatically
decreasing the output voltage. When the output current falls within
the rated range, the overload protection function is automatically
cleared.
The values shown in the above diagrams are for reference only.
Note: 1. If the S82J is connected to a load with a built-in DC-DC
600-W Models
If an excessive current flows for 5 s or more, the output will be turned
OFF and simultaneously the protection-ON alarm indicator will be lit.
To reset the S82J, turn OFF the power, leave the S82J for at least
three minutes, and then turn it ON again.
10 W, 25 W Models
50 W, 100 W (24-V) Models
100 W (5-V, 12-V, 15-V), 150 W, 300 W Models
0
2. Internal parts may occasionally deteriorate or be damaged
3. In actual operation, the output voltage may not fall to 0 V
4. The overload protection function is specified at 105% or
converter, the overload protection function may be triggered
at startup, and consequently the S82J may not operate.
if a short-circuited or other overcurrent state continues
during operation.
Eliminate the overcurrent state as soon as possible.
when the overload protection function is triggered. Even
with short-circuits on the load side, the drop in voltage will
vary depending on factors such as the impedance in the
load line.
more of the rated output current for 300-W models.
50
Output current (%)
0
0
0
Intermitted operation
Intermitted operation
100
50
50
50
Output interrupted
Output current (%)
Output current (%)
Output current (%)
100
100
100
Note: Internal parts may occasionally deteriorate or be damaged if a
■ Overvoltage Protection
100-W (5-, 24-V Output) Models
Consider the possibility of an overvoltage and design the system so
that the load will not be subjected to an excessive voltage even if the
feedback circuit in the Power Supply fails. When an excessive
voltage that is approximately 120% of the rated voltage or more is
output, the output voltage is shut OFF, preventing damage to the load
due to overvoltage. Reset the input power by turning it OFF for at
least one minute and then turning it back ON again.
The values shown in the above diagram are for reference only.
300- and 600-W Models
When an excessive voltage that is approximately 120% of the rated
voltage or more is output, the output voltage will be turned OFF and
simultaneously the protection-ON alarm indicator will be lit. Reset the
input power by turning it OFF for at least three minutes (90 seconds
for 300-W models) and then turning it back ON again.
■ Overheat Protection Function
600-W Models Only
If the internal temperature rises excessively as a result of fan failure
or any other reason, the overheat protection circuit will be triggered
to protect the internal parts and simultaneously the protection-ON
alarm indicator will be lit. Reset the input power by turning it OFF for
at least three minutes and then turning it back ON again.
■ Inrush Current, Startup Time,
Note: Models with a 100 to 240 V (free) input have a higher inrush
AC input
voltage
AC input
current
Output
voltage
Hold Time
short-circuited state continues during operation.
Eliminate the overcurrent state as soon as possible.
current energy than models with a single rated input voltage or
models with a switchable input voltage. Be sure to coordinate
breaker with the inrush current energy.
Input ON
Rated output
voltage
Inrush current on input application
Startup time
Voltage
adjustable range
90%
(20 ms min.)
Overvoltage
protection
operates
Hold time
Input OFF
S82J
96.5%
10

Related parts for S82Y-JFAN