Specifications of S82Y-G03B

Accessory Type
Mounting Bracket(s)
For Use With/related Products
S82G-03xx Power Supply
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
S82YG03B
Nomenclature
Operation

S82G
1. DC Output Terminals: Connect load wiring.
2. Input Terminals: Connect input wiring.
3. Input Voltage Selector Terminals: Switch the input
4. V. ADJ Adjuster: Use to adjust the output voltage.
5. Output LED Indicator: Lights when DC current is being
6. Remote Sensing Terminals: Correct the voltage drop in
7. Remote Control Terminals: Turn the output ON or OFF,
Note: 1. When a high voltage drops occur on the load lines, the

This function corrects a voltage drop in the load lines. When using
the remote sensing function, remove the short bars from the remote
sensing terminals as shown in the following diagram.
Remote sensing connection
(2-wire shielded cable)
voltage by connecting or removing the short bar. (short
circuited: 100 to 120 V; open: 200 to 240 V).
output.
the load lines. Shorted for normal operation.
by using an external signal, with the input voltage
applied.
S82G-03
S82G-06
S82G-10
S82G-15
Load
REMOTE SENSING FUNCTION
2. When the +S and +V terminals, or -V and -S terminals
Load lines
output voltage across the power terminals rises by the
amount of the dropped voltage, causing the overvoltage
protection function to be effected. To prevent this, use as
thick a wire as possible.
are opened with the short bar removed, the overvoltage
protection function is effected and, as a result, no output
voltage is produced.




V ADJ DC ON
V ADJ
Remove the
short bars
DC ON
24 VDC, 13 A
AC1
N
+S
+V
-V
-S
FG
8. ACG Terminal: Input filter neutral terminal, which is
9. FG Terminal: Short-circuited to the housing and is
10. NC Terminal: Vacant terminals.
11. Short Bars:

This function allows the output voltage to be turned on and
off with an external signal (as long as the input voltage is
being applied). When using the remote control function,
remove the short bar (as set by the factory) from the remote
control terminals and connect a switch or transistor, across
those terminals, as shown in the diagram below
usually short-circuited to the FG terminal.
connected to a ground line.
Switch or Transistor
ON
OFF
REMOTE CONTROL FUNCTION
V ADJ
DC ON
+S
+V
+V
+RC
-V
-V
-S
-RC
NC
24 VDC, 7 A
FG
INPUT
Output voltage
ON
OFF
NC
L
N
Remove the short bar
S82G