FE1000-48NA TDK Corporation, FE1000-48NA Datasheet - Page 7

no-image

FE1000-48NA

Manufacturer Part Number
FE1000-48NA
Description
POWER SUPPLY COMPACT RACK MOUNT
Manufacturer
TDK Corporation
Series
FEr
Datasheet

Specifications of FE1000-48NA

Voltage - Output
48V
Number Of Outputs
1
Power (watts)
1000W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
48 VDC @ 21A
Size / Dimension
11.97" L x 5" W x 3.3" H (304mm x 127mm x 83.8mm)
Power (watts) - Rated
1000W
Operating Temperature
-40°C ~ 70°C
Efficiency
82%
Approvals
CE, CSA, EN, IEC, UL
Line Regulation
±1%
Load Regulation
±1%
3rd Output
-
2nd Output
-
4th Output
-
Other names
Q1001884
FE S
I
M
ERIES
NSTRUCTION
ANUAL
Lambda FE Series Safety and Installation Instructions for Lambda Model FE1000
To comply with published safety standards, the following instructions must be used in conjunction
with the Lambda FE Series:
For earth fault protection, the unit must be protected in the final installation by suitable overcurrent
protection means. If protection relies upon building wiring, the end product installation must
ensure that the necessary protection is provided.
The internal fuse (F101) may only be replaced with a Littelfuse, type 324015, rated at 15A, 250V.
The power supply is intended for use as a component of other equipment. When installing the
power supply, the relevant safety standards (EN60950, IEC950, UL1950 or CSA-22.2-950) must
be complied with.
In particular, creepage and clearance distances and distances through insulation between primary
and earth or primary and secondary must be maintained.
The power supply output is SELV in accordance with requirements IEC-950. The output available
has power greater than 240VA.
The CE mark on the product is applied to show conformance with the requirements outlined in the
European Union’s Low Voltage Directive [72/23/EEC] as amended by the CE Mark Directive
[93/68/EEC].
The maximum ambient temperature of the operating environment must not exceed 50ºC at
1000W, 60ºC at 750W or 70ºC at 500W.
This unit is protected by an approved fuse rated at a maximum 20A, 250VAC for 110VAC
installations (10A, 250VAC for 220VAC installations) and is to be placed in the ungrounded supply
conductor.
For continuous operation at 85VAC input, an approved 20A line cord is required.
LAMBDA ELECTRONICS INCOPORATED
515 BROAD HOLLOW ROAD, MELVILLE, NY 11747-3700 • TEL: 516-694-4200 • 516-293-0519
P. 7
IMFE1000

Related parts for FE1000-48NA