FE-1500-48-NA TDK Corporation, FE-1500-48-NA Datasheet - Page 4

no-image

FE-1500-48-NA

Manufacturer Part Number
FE-1500-48-NA
Description
POWER SUPPLY 1500W 48V 32A
Manufacturer
TDK Corporation
Series
FEr
Datasheet

Specifications of FE-1500-48-NA

Voltage - Output
48V
Number Of Outputs
1
Power (watts)
1500W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
85 ~ 265VAC
Mounting Type
Chassis Mount
1st Output
48 VDC @ 32A
Size / Dimension
11.97" L x 5" W x 5" H (304mm x 127mm x127mm)
Power (watts) - Rated
1500W
Operating Temperature
-40°C ~ 70°C
Efficiency
82%
Approvals
CE, CSA, EN, IEC, UL
Line Regulation
±1%
Load Regulation
±1%
3rd Output
-
2nd Output
-
4th Output
-
Other names
Q811394
LAMBDA ELECTRONICS
FEATURES:
I. DC OUTPUT, CONTROLS AND INDICATORS
OUTPUT VOLTAGE ADJUST
OVERVOLTAGE
PROTECTION ADJUST
OUTPUT-INVERTER GOOD
INDICATOR
AC GOOD INDICATOR
OVERTEMPERATURE FAULT
INDICATOR
LOAD CURRENT INDICATOR
II. REMOTE CONTROL FEATURES
REMOTE VOLTAGE SENSING
REMOTE ON-OFF CONTROL
SIGNAL ISOLATION
III. AUXILIARY MONITORING AND ALARM SIGNALS — OPTICALLY COUPLED, CONDUCTANCE OUTPUTS.
(CONDUCT UP TO 5mA AT A VOLTAGE OF LESS THAN 1.0VDC WHEN ACTIVE.)
AC FAIL SIGNAL
OUTPUT-INVERTER GOOD
SIGNAL
OUTPUT CURRENT MONITOR
SIGNAL
SIGNAL ISOLATION
DESCRIPTION
DESCRIPTION
DESCRIPTION
515 BROAD HOLLOW ROAD, MELVILLE, NY 11747-3700 • TEL: 516-694-4200 • 516-293-0519
FACTORY SET AT 24VDC OR 48VDC. CONSULT FACTORY FOR
ADJUSTMENT.
FACTORY SET AT 30VAC OR 60VDC. CONSULT FACTORY FOR
ADJUSTMENT.
GREEN-COLORED LED ILLUMINATES WHEN THE OUTPUT IS WITHIN THE
SPECIFIED OPERATING RANGE AND THE INVERTER IS PROPERLY
FUNCTIONING.
GREEN-COLORED LED ILLUMINATES TO INDICATE AC POWER IS APPLIED.
RED-COLORED LED ILLUMINATES IF OVERTEMPERATURE SHUTDOWN
OCCURS.
FIVE GREEN-COLORED LEDs INDICATE APPROXIMATE PERCENTAGE OF
OUTPUT CURRENT VALUE.
PROVIDES PRECISE REGULATION DIRECTLY AT LOAD. THE MAXIMUM
TOTAL DC VOLTAGE DROP BETWEEN THE OUTPUT TERMINALS AND THE
LOAD MUST BE LIMITED TO LESS THAN 1.0 VOLT FOR -NA MODELS AND 0.5
VOLTS FOR -RA MODELS.)
DC OUTPUT IS ENABLED VIA A CONNECTION BETWEEN PINS 6 AND 19 OF
25-PIN, D CONNECTOR.
REMOTE ON-OFF PINS ARE REFERENCED TO THE -V
CONDUCTANCE SIGNAL WHICH INDICATES SUFFICIENT AC INPUT IS
PRESENT TO PROVIDE A MINIMUM OF FIVE MILLISECONDS OF HOLD-UP
TIME AFTER THE REMOVAL OF INPUT.
CONDUCTANCE SIGNAL WHICH INDICATES THAT DELIVERED OUTPUT
VOLTAGE, AS MEASURED AT THE +V AND -V TERMINALS, IS PRESENT AND
THE INVERTER IS OPERATIONAL.
ZERO TO ONE VOLT SIGNAL PROPORTIONAL TO OUTPUT CURRENT
AVAILABLE FOR MONITORING. ONE VOLT CORRESPONDS TO 100
PERCENT RATED CURRENT.
SIGNALS ARE ISOLATED FROM POWER SUPPLY OUTPUT AND EACH
OTHER FOR VOLTAGES UP TO 500VDC MAXIMUM AND 3000VAC ISOLATION
FROM AC INPUT TO AUXILIARY SIGNALS. THE CURRENT MONITOR SIGNAL
IS REFERENCED TO THE -IMON TERMINAL (THE CATHODE OF THE
INTERNAL OR-ING DIODE.)
LAMBDA ELECTRONICS INCOPORATED
FE S
ERIES
I
P. 4
NSTRUCTION
OPERATIONAL DEFINITION
OPERATIONAL DEFINITION
OPERATIONAL DEFINITION
M
ANUAL
OUT
TERMINAL.
IMFE1500