S82J-10015D Omron, S82J-10015D Datasheet - Page 8

POWER SUPPLY SWITCHING 15V 7A

S82J-10015D

Manufacturer Part Number
S82J-10015D
Description
POWER SUPPLY SWITCHING 15V 7A
Manufacturer
Omron
Series
S82Jr
Datasheets

Specifications of S82J-10015D

Voltage - Output
15V
Number Of Outputs
1
Power (watts)
100W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
120, 240VAC
Mounting Type
Chassis Mount
1st Output
15 VDC @ 7A
Size / Dimension
3.82" L x 7.4" W x 1.97" H (97mm x 188mm x 50mm)
Power (watts) - Rated
100W
Operating Temperature
-10°C ~ 60°C
Efficiency
75%
Approvals
CE, CSA, UL, VDE
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
S82J10015D
J OVERHEAT PROTECTION FUNCTION
600-W Model Only
If the internal temperature of the S82J rises excessively as a
result of fan failure or any other reason, the overheat protection
circuit will be triggered to protect the internal elements of the
S82J and simultaneously a protection-ON alarm indicator will be
lit. To reset the S82J, turn off the input voltage, leave the S82J for
at least three minutes, and then apply the input voltage again.
J OVERVOLTAGE PROTECTION
100-W (5, 24 V) Output Models
These power supplies have an overvoltage protection
function that protects the load and the power supply from
possible damage by overvoltage. When the output voltage
rises above a set value (120% of the rated output voltage),
the protection function is triggered, shutting off the output
voltage. If this occurs, reset the power supply by turning it off
for 1 minute minimum and then turning it on again.
300- and 600-W Models
If a voltage that is 120% of the rated output voltage or above is
output, the output voltage will be turned off and simultaneously
protection-ON alarm indicator will be lit. To reset the S82J, turn
off the input voltage, leave the S82J for at least three minutes if
it is a 600-W model or at least 90 seconds if it is a 300-W model,
and then apply the input voltage again.
J INRUSH CURRENT, START UP TIME, HOLD TIME
AC input voltage
AC input current
Output voltage
Input ON
Inrush current on input application
Start up time
90%
Input OFF
Note: The output voltage can be varied by the V. ADJ
Hold time
(20 ms min.)
Rated output
voltage
Switching Power Supply
96.5%
adjuster on the front panel. When it is set to a
value 10% higher than the rated value, the over-
voltage protection function may be effected.
Approx.
20%
10%
–10%
Variable range
S82J
Overvoltage
protection
operating
8