2938219 Phoenix Contact, 2938219 Datasheet - Page 2

POWR SUPPLY 10A 3X400-500AC 48DC

2938219

Manufacturer Part Number
2938219
Description
POWR SUPPLY 10A 3X400-500AC 48DC
Manufacturer
Phoenix Contact
Series
Quintr
Type
Industrialr
Datasheets

Specifications of 2938219

Voltage - Output
48V
Number Of Outputs
1
Power (watts)
480W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
400 ~ 500VAC
Mounting Type
DIN Rail
1st Output
48 VDC @ 10A
Size / Dimension
5.12" L x 6.30" W x 5.12" H (130mm x 160mm x 130mm)
Power (watts) - Rated
480W
Operating Temperature
-25°C ~ 70°C
Efficiency
90%
Approvals
CB, cUL, UL
Product
Switching
Commercial/medical
Commercial
Output Power Rating
480 W
Input Voltage
3 x 400 VAC to 500 VAC
Output Voltage (channel 1)
48 VDC
Output Current (channel 1)
10 A
Mounting Style
DIN Rail
Brand/series
QUINT-PS
Configuration
Enclosed
Current, Inrush
10
Current, Rating
10 A
Frequency
45 to 65 Hz
Height
130 mm
Operation
Switching
Output
48 VDC @ 10 A
Phoenix Part Number
QUINT-PS-3x400-500AC/48DC/10
Power, Output
45 W
Primary Type
AC-DC
Temperature, Operating, Maximum
+70 °C (Ambient)
Temperature, Operating, Minimum
-25 °C (Ambient)
Voltage, Input
320 to 575/450 to 800 VAC/VDC
Voltage, Output
48 VDC
Voltage, Rating
320 to 575 VAC
Width
160 mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-1920
QUINT-PS3X400-500AC/48DC/10
QUINT-PS-3X400-500AC/48DC/10
PHOENIX CONTACT Inc., USA
DC frequency range
Current consumption
Nominal power consumption
Inrush surge current
Power failure bypass
Recommended backup fuse
Name of protection
Protective circuit/component
Output data
Nominal output voltage
Setting range of the output voltage
Output current
Connection in parallel
Connection in series
Residual ripple
Peak switching voltages nominal load
Maximum power dissipation idling
Power loss nominal load max.
General data
Width
Height
Depth
Weight
Efficiency
Insulation voltage input/output
Degree of protection
Class of protection
MTBF
Order No.: 2938219
0 Hz
Approx. 3x 1.2 A (400 V AC)
1 A (480 V AC)
480 W
< 10 A
> 25 ms (400 V AC)
> 30 ms (480 V AC)
3 x 6 A
10 A
16 A (characteristic B)
Transient surge protection
Varistor
48 V DC ±1%
30 V DC ... 56 V DC (> 48 V constant capacity)
10 A (-25°C ... 70°C)
13 A (with POWER BOOST, -25°C ... 40°C permanent)
Yes, for redundancy and increased capacity
Yes
< 20 mVPP
< 140 mVPP (20 MHz)
10 W
45 W
160 mm
130 mm
130 mm
2.3 kg
> 90 % (At 230 V AC and nominal values)
3 kV (type test)
1.5 kV (routine test)
IP20
I, with PE connection
> 500 000 h in acc. with IEC 61709 (SN 29500)
Page 2 / 6