S8TS-06024-E1. Omron, S8TS-06024-E1. Datasheet - Page 12

no-image

S8TS-06024-E1.

Manufacturer Part Number
S8TS-06024-E1.
Description
BLOCK BASIC 24V 2.5A SCREW TERM
Manufacturer
Omron
Series
S8TSr
Datasheets

Specifications of S8TS-06024-E1.

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
60W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 2.5A
Size / Dimension
4.72" L x 1.69" W x 4.72" H (120mm x 43mm x 120mm)
Power (watts) - Rated
60W
Operating Temperature
-10°C ~ 50°C
Efficiency
75%
Approvals
CE, cUL, cUR, UL, VDE
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
S8TS06024E1
Safety Precautions
Refer to Safety Precautions for All Power Supplies.
■ Precautions for Safe Use
Mounting
To improve the long-term reliability of devices, give due consideration
to heat dissipation when mounting. With the S8TS, heat is dissipated
by natural convection. Mount Blocks in a way that allows convection
in the atmosphere around them.
*1. Convection of air
*2. 75 mm min.
*3. 75 mm min.
*4. 10 mm min.
When cutting out holes for mounting, make sure that cuttings do not
enter the interior of the products.
Electric shock may occur. Do not link or unlink Power
Supplies while input power is ON.
Electric shock may occur. Do not remove the connector
cover from the Bus Line Connector if the Power Supply is
not linked.
Electric shock may occur. Close the terminal cover before
using the Power Supply.
Always lock the sliders and rail stoppers when using
linked Power Supplies.
When linking Power Supplies, connect the input power to
only one Power Supply. If the input power is not wired
correctly, an internal short-circuit will occur and the Power
Supplies will be damaged.
Fire may occur if screws become loose. Tighten terminal
screws to a torque of 1.08 N·m, and tighten connector
screws and flanges to a torque of 0.30 N·m.
!CAUTION
*1
*1
*4
*1
*1
*2
*3
Wiring
Connect the ground completely. Electric shock or malfunction may
occur if the ground is not connected completely.
Minor fire may possibly occur. Ensure that input and output terminals
are wired correctly.
Do not apply more than 100-N force to the terminal block when
tightening it.
Be sure to remove the sheet covering the Power Supply for
machining before turning ON the power so that it does not interfere
with heat dissipation.
Use the following material for the wires to be connected to the S8TS
to prevent smoking or ignition caused by abnormal loads.
Recommended Wire Size for Single-unit
Operation
Recommended Wire Size for Parallel
Operation
Blocks with Connector Terminals
When using Blocks with connector terminals, the current for
1 terminal must not exceed 7.5 A. If a higher current is required, use
2 terminals.
Do not insert/remove AC input connectors or DC output connector
more than 20 times.
Installation Environment
Do not use the Power Supply in locations subject to shocks or
vibrations. In particular, install the Power Supply as far as possible
from contactors or other devices that are a vibration source. Be sure
to mount End Plates (PFP-M) on both ends of the Power Supply.
Install the Power Supply well away from any sources of strong, high-
frequency noise and surge.
S8TS-02505
S8TS-03012
S8TS-06024
S8TS-02505F
S8TS-03012F
S8TS-06024F
S8TS-03012
S8TS-06024
S8TS-03012F
S8TS-06024F
Model
Model
For 2 Units con-
nected in parallel
For 3 Units con-
nected in parallel
For 4 Units con-
nected in parallel
For 2 Units con-
nected in parallel
For 3 Units con-
nected in parallel
For 4 Units con-
nected in parallel
AWG 14 to 18 (cross-sectional area: 0.823
to 2.081 mm
AWG 14 to 18 (cross-sectional area: 0.823
to 2.081 mm
AWG 12 to 18 (cross-sectional area: 0.823
to 3.309 mm
AWG 12 to 20 (cross-sectional area: 0.517
to 3.309 mm
Recommended wire size
AWG 14 to 18 (cross-sectional ar-
ea: 0.823 to 2.081 mm
AWG 14 to 16 (cross-sectional ar-
ea: 1.309 to 2.081 mm
AWG 14 (cross-sectional area:
2.081 mm
AWG 12 to 18 (cross-sectional ar-
ea: 0.823 to 3.309 mm
AWG 12 to 16 (cross-sectional ar-
ea: 1.309 to 3.309 mm
AWG 12 to 14 (cross-sectional ar-
ea: 2.081 to 3.309 mm
Recommended wire size
2
2
2
2
)
)
)
)
2
)
2
2
2
2
2
S8TS
)
)
)
)
)
12