2866763 Phoenix Contact, 2866763 Datasheet - Page 3

POWER SUPPLY 10A 85-264AC 24DC

2866763

Manufacturer Part Number
2866763
Description
POWER SUPPLY 10A 85-264AC 24DC
Manufacturer
Phoenix Contact
Series
Quintr
Type
Industrialr
Datasheets

Specifications of 2866763

Voltage - Output
24V
Number Of Outputs
1
Power (watts)
240W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 10A
Size / Dimension
4.92" L x 2.36" W x 5.12" H (125mm x 60mm x 130mm)
Power (watts) - Rated
240W
Operating Temperature
-25°C ~ 70°C
Efficiency
92.5%
Approvals
ABS, BV, CB, CSA, cUL, DNV, GL, LR, NK, UL
Product
Switching
Commercial/medical
Commercial
Output Power Rating
240 W
Input Voltage
100 VAC to 240 VAC
Output Voltage (channel 1)
24 VDC
Output Current (channel 1)
10 A
Mounting Style
DIN Rail
Brand/series
QUINT-PS
Configuration
Enclosed
Operation
Switching
Output
24 VDC @ 10 A
Phoenix Part Number
QUINT-PS/1AC/24DC/10
Power, Output
18 W
Primary Type
AC-DC
Voltage, Input
85 - 264/90 - 350 VAC/VDC
Voltage, Output
24 VDC
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
277-1994
QUINT-PS/ 1AC/24DC/10
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2866763
PHOENIX CONTACT Inc., USA
http://www.phoenixcon.com
General data
Width
Height
Depth
Weight
Efficiency
Insulation voltage input/output
Degree of protection
Class of protection
MTBF
Ambient temperature (operation)
Ambient temperature (storage/transport)
Max. permissible relative humidity (operation)
Mounting position
Assembly instructions
Electromagnetic compatibility
Emitted interference
Immunity to interference
Standard – Electrical equipment of machines
Standard - Safety of transformers
Standard - Electrical safety
Shipbuilding approval
Standard – Electronic equipment for use in
electrical power installations and their assembly
into electrical power installations
Standard – Safety extra-low voltage
Standard - Safe isolation
Standard – Protection against electric shock
Standard – Protection against shock currents,
basic requirements for protective separation in
electrical equipment
Standard – Limitation of mains harmonic currents
Standard – Equipment safety
Order No.: 2866763
60 mm
130 mm
125 mm
1.1 kg
> 92.5 % (for 230 V AC and nominal values)
4 kV AC (type test)
2 kV AC (routine test)
IP20
I, with PE connection
> 500 000 h in acc. with IEC 61709 (SN 29500)
-25 °C ... 70 °C (> 60 °C derating)
-40 °C ... 85 °C
95 % (at 25 °C, no condensation)
Horizontal DIN rail NS 35, EN 60715
Can be aligned: horizontally 5 mm, in addition to active
components of 15 mm, vertically 5 cm
Conformance with EMC guideline 2004/108/EC and for low-
voltage guideline 2006/95/EC
EN 50081-2
EN 61000-6-2:2005
EN 60204
IEC 61558-2-17
IEC 60950/VDE 0805 (SELV)
Germanischer Lloyd (EMC 1), ABS, LR, RINA, NK, DNV, BV
EN 50178/VDE 0160 (PELV)
IEC 60950 (SELV) and EN 60204 (PELV)
DIN VDE 0100-410
DIN VDE 0106-1010
DIN 57100-410
DIN VDE 0106-101
EN 61000-3-2
GS (tested safety)
Mar 23, 2010