D1U-H-2800-52-HB1C Murata Power Solutions Inc, D1U-H-2800-52-HB1C Datasheet - Page 3

POWER SUPPLY 2800W AC/DC -52V

D1U-H-2800-52-HB1C

Manufacturer Part Number
D1U-H-2800-52-HB1C
Description
POWER SUPPLY 2800W AC/DC -52V
Manufacturer
Murata Power Solutions Inc
Series
D1U-H-2800-52-HBxCr
Datasheet

Specifications of D1U-H-2800-52-HB1C

Voltage - Output
-52V
Number Of Outputs
1
Power (watts)
2800W
Applications
Commercial
Power Supply Type
Switching (Closed Frame)
Voltage - Input
170 ~ 264VAC
Mounting Type
Chassis Mount
1st Output
-52 VDC @ 54A
Size / Dimension
11.5" L x 5.5" W x 1.6" H (292.1mm x 140mm x 41mm)
Power (watts) - Rated
2800W
Operating Temperature
0°C ~ 50°C
Efficiency
91.6%
Approvals
c-CSA-us, CSA, UL
Output Voltage (channel 1)
- 52 V
Dimensions
11.5 in L x 5.5 in W x 1.6 in H
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
811-1949
CONTROL SIGNALS
Status
LED
FANS MONITORING
Status
Fans monitoring is available through the I2C interface
EMISSIONS AND IMMUNITY
Characteristic
Harmonics
Voltage Fluctuation and Flicker
Emission Conducted
Emission Radiated
ESD
Electromagnetic Field
Electrical Fast Transients/Burst
Surge
RF Conducted Immunity
Magnetic Immunity
Voltage dips, interruptions
www.murata-ps.com
Conditions
Off
Flashing Yellow
Flashing Green
Green
Conditions
Both fans running normally
One fan failed (or rotor locked)
Both fans failed (or rotors locked)
Description
IEC/EN 61000-3-2
IEC/EN 61000-3-3
FCC 47 CFR Parts 15/CISPR 22/EN55022
FCC 47 CFR Parts 15/CISPR 22/EN55022
IEC/EN 61000-4-2
IEC/EN 61000-4-3
IEC/EN 61000-4-4
IEC/EN 61000-4-5
IEC/EN 61000-4-6
IEC/EN 61000-4-8
IEC/EN 61000-4-11
D1U-H-2800-52-HBxC Series
Technical enquiries email: toronto@murata-ps.com, tel:
Description
No AC input to all PS
Power Supply Failure
Main Output Absent
Power Supply Good
Description
PS_Fault0 bits 3 and 4 set to “0”
PS_Fault0 bit 4 set to “1”
PS_Fault0 bits 3 and 4 set to “1”
Criteria
Class A, 6dB margin
Class A, 6dB margin
4kV contact discharge
8kV operational air discharge
15kV non-operational air discharge
1kV/2kV, Performance Criteria B
3 Vac, 80% AM, 1kHz, Performance Criteria A
3 A/m
AC/DC Front End Power Supply
D1U-H-2800-52-HBxC.A06 Page 3 of 5
+1 (866) 740 1232

Related parts for D1U-H-2800-52-HB1C