S8VS-24024 Omron, S8VS-24024 Datasheet - Page 14

POWER SUPPLY SW 24VDC 10A 240W

S8VS-24024

Manufacturer Part Number
S8VS-24024
Description
POWER SUPPLY SW 24VDC 10A 240W
Manufacturer
Omron
Series
S8VSr
Datasheets

Specifications of S8VS-24024

Power Supply Type
Switching (Closed Frame)
Input Voltage
100 VAC to 240 VAC
Voltage - Output
24V
Number Of Outputs
1
Power (watts)
240W
Applications
Commercial
Voltage - Input
100 ~ 240VAC
Mounting Type
DIN Rail
1st Output
24 VDC @ 10A
Size / Dimension
4.93" L x 3.94" W x 4.53" H (125.3mm x 100mm x 115mm)
Power (watts) - Rated
240W
Operating Temperature
-10°C ~ 60°C
Efficiency
80%
Approvals
CE, CSA, cUL, EN, UL, VDE
Product
Switching
Output Power Rating
240 W
Output Voltage (channel 1)
24 V
Output Current (channel 1)
10 A
Mounting Style
DIN Rail
Dimensions
125.3 mm L x 100 mm W x 115 mm H
Open Frame/enclosed
Enclosed
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
24V
Output Current
10A
Power Rating
240W
Length
125.3mm
Width
100mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
S8VS24024
Z2301
Construction and Nomenclature (15-W, 30-W Models)
Nomenclature
15-W, 30-W Models
Note: The S8VS-01505 is shown above.
Engineering Data (15-W, 30-W Models)
Derating Curve
S8VS-015@@
S8VS-03005/S8VS-03012
120
100
120
100
80
60
40
20
80
60
40
20
−20
−20
*1 Standard mounting
*2 Face-up mounting/Horizontal mounting
*1 Standard mounting
*2 Face-up mounting
*3 Horizontal mounting
0
0
−10
−10
0
0
10
10
20
20
1
2
4
5
6
3
30
30
Ambient temperature (°C)
Ambient temperature (°C)
40
40
*1. The fuse is located on the (L) side. It is NOT user-replaceable.
*2. This is the protective earth terminal specified in the safety standards. Always ground this terminal.
No.
1
2
3
4
5
6
50
50
AC Input terminals (L), (N)
Protective Earth terminal (PE)
DC Output terminals (−V), (+V)
Output indicator (DC ON: Green)
Undervoltage indicator (DC LOW: Red) Lights when a drop is detected in the output voltage.
Output voltage adjuster (V.ADJ)
60
60
1
1
70 80
70 80
*1
*2
*3
*1
*2
Name
Connect the input lines to these terminals. *1
Connect the ground line to this terminal. *2
Connect the load lines to these terminals.
Lights while a direct current (DC) output is ON.
Use to adjust the voltage.
S8VS-015@@/S8VS-030@@
S8VS-03024
Note: 1. Internal parts may occasionally deteriorate or be damaged.
120
100
80
60
40
20
−20
0
*1 Standard mounting
*2 Face-up mounting/Horizontal mounting
2. If there is a derating problem, use forced air-cooling.
3. Provide a space of at least 20 mm when using standard
−10
Do not use the Power Supply in areas outside the derating
curve (i.e., the area shown by shading A in the above
graph).
mounting and horizontal mounting. If 20 mm is not available,
make sure that the space is at least 10 mm. In this case,
reduce the corresponding derating curve by 5°C.
0
10
20
30
Ambient temperature (°C)
Function
40
50
60
1
70 80
*1
*2
S8VS
14

Related parts for S8VS-24024