SU5000RT3U Tripp Lite, SU5000RT3U Datasheet - Page 5

UPS SMARTONLINE 5KVA 3500W 16OUT

SU5000RT3U

Manufacturer Part Number
SU5000RT3U
Description
UPS SMARTONLINE 5KVA 3500W 16OUT
Manufacturer
Tripp Lite
Series
Smart Online™r
Type
Power Supply Regulatorr
Datasheet

Specifications of SU5000RT3U

Power - Rated
5kVA / 3500W
Ac Outlets
16 (UPS)
Features
DB9 Communications, SNMP Card Slot
Backup Time - Max Load
8 minutes
Voltage - Output Per Connector
208V
Voltage - Input
208V / 30A
Cord Length
10' (3.05m)
Ac Input Connector
NEMA L6-30P
Connector - Ac Output
1 NEMA L6-30R, 2 NEMA L6-20R and 8 NEMA 5-15/20R
Size
26.00" L x 17.50" W x 5.25" H (660.4mm x 444.5mm x 133.4mm)
Weight
42 lbs (19.1kg)
Ac Output Connector
1 NEMA L6-30R, 2 NEMA L6-20R and 8 NEMA 5-15/20R
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Media Lines Protected
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Stepdown transformer
weight (kg)
Included battery pack
dimensions (height x
width x depth / inches)
Included battery pack
dimensions (height x
width x depth / cm)
Included battery pack
weight (lbs)
Included battery pack
weight (kg)
Shipping weight (lbs)
Shipping weight (kg)
UPS housing material
Cooling method
ENVIRONMENTAL
Operating Temperature
Range
Storage Temperature
Range
Relative Humidity
AC mode BTU / hr. (full
load)
AC economy mode
BTU / hr. (full load)
Battery mode BTU / hr.
(full load)
AC economy mode
efficiency rating (100%
load)
COMMUNICATIONS
Communications
interface
Network monitoring
port description
PowerAlert software
Communications cable
LINE / BATTERY TRANSFER
Transfer time
Low voltage transfer to
battery power (setpoint)
High voltage transfer to
battery power (setpoint)
SPECIAL FEATURES
25.9
3.5 x 17.5 x 22.5
8.9 x 44.4 x 57.2
92
41.8
256
116.2
Steel
Fan
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
0 to 95%, non-condensing
1322.2
759.6
1322.2
94%
DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
RS232 and contact closure communications are located on two separate DB9 ports
Included
DB9 cable included
No transfer time (0 ms.) in online, double-conversion mode
156
276

Related parts for SU5000RT3U