SMART1200XLHG Tripp Lite, SMART1200XLHG Datasheet - Page 3

UPS 1KVA 4OUT 1DB9/1USB HOSP GRD

SMART1200XLHG

Manufacturer Part Number
SMART1200XLHG
Description
UPS 1KVA 4OUT 1DB9/1USB HOSP GRD
Manufacturer
Tripp Lite
Series
Smart Pro®r
Type
UPSr
Datasheet

Specifications of SMART1200XLHG

Rohs Status
Not applicable
Power - Rated
1kVA / 750W
Ac Outlets
4 (UPS)
Features
Hospital Grade
Backup Time - Max Load
16 minutes
Voltage - Output Per Connector
120V
Voltage - Input
120V / 15A
Cord Length
6' (1.83m)
Ac Input Connector
NEMA 5-15P HG
Connector - Ac Output
NEMA 5-15R HG
Size
9.50" L x 7.50" W x 12.50" H (241.3mm x 190.5mm x 317.5mm)
Weight
45 lbs (20.4kg)
Ac Output Connector
NEMA 5-15R HG
Power Rating
1000 VA
Output Voltage Rating
120 V
Number Of Outlets
4
Interface Port
USB / DB9
Runtime (full Load)
16 min
Runtime (half Load)
34 min
Topology
Line Interactive
Tower / Rackmount
Tower
Media Lines Protected
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
TL252
Half load runtime (minutes)
Expandable battery runtime
External battery pack
compatibility
DC system voltage (VDC)
Battery recharge rate
(included batteries)
Replacement battery
cartridge (internal UPS
battery replacement)
Battery Access
Battery replacement
description
VOLTAGE REGULATION
Voltage regulation
description
Overvoltage correction
Undervoltage correction
Severe undervoltage
correction
LEDS ALARMS & SWITCHES
LED Indicators
Alarms
Alarm cancel operation
Switches
SURGE / NOISE SUPPRESSION
UPS AC suppression joule
rating
UPS AC suppression
response time
EMI / RFI AC noise
suppression
ISOLATION
Output isolation
transformer
Leakage current
PHYSICAL
Installation form factors
supported with included
accessories
Installation form factors
supported with optional
accessories
28 min. (375w)
Extended runtime supported via optional external battery packs
BP36V15-2U
36
Less than 4.5 hours from 10% to 90%
RBC53
Battery access door
Hot-swappable, user replaceable batteries
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 81 to 143
Input voltages between 126 and 143 are reduced by 9%
Input voltages between 96 and 106 are boosted by 10%
Input voltages between 81 and 95 are boosted by 21%
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status
Audible alarm indicates power-failure, overload and low-battery conditions
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate
low-battery status
2 Switches control off/on power status and alarm-cancel/self-test operation
480
Instantaneous
Yes
Hospital grade load isolation transformer
Equal to 100 microamps
Tower
Wallmount (UPSWM - tower mounting kit)
(limit 1);
BP36V42-3U
(multi-pack compatible)

Related parts for SMART1200XLHG