SMART1500RMXL2UA Tripp Lite, SMART1500RMXL2UA Datasheet - Page 3

UPS 1500VA 1000W 8OUT W/SOFTWARE

SMART1500RMXL2UA

Manufacturer Part Number
SMART1500RMXL2UA
Description
UPS 1500VA 1000W 8OUT W/SOFTWARE
Manufacturer
Tripp Lite
Series
Smart Pro®r

Specifications of SMART1500RMXL2UA

Rohs Status
Not applicable
Power - Rated
1.5kVA / 1000W
Ac Outlets
8 (UPS)
Features
DB9 and USB Communications, Rack Mount
Backup Time - Max Load
10 minutes
Voltage - Output Per Connector
120V
Voltage - Input
120V / 15A
Cord Length
10' (3.05m)
Ac Input Connector
NEMA 5-15P
Connector - Ac Output
NEMA 5-15R
Weight
52 lbs (23.6kg)
Ac Output Connector
NEMA 5-15R
Size
-
Media Lines Protected
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Other names
TL308
Outlet quantity / type:
Customized load management receptacles: Individually controllable pair of outlets support automated load shedding and remote reboot
Overload protection:
INPUT
Maximum input amps / watts:
Input connection type:
Input cord length:
Recommended electrical service:
BATTERY
Full load runtime:
Half load runtime:
DC system voltage:
Typical battery lifespan:
Battery recharge rate:
Expandable battery runtime:
VOLTAGE REGULATION
Voltage regulation description:
Overvoltage correction:
Direct pass through:
Brownout correction:
Severe brownout correction:
LEDS ALARMS & SWITCHES
Front panel LEDs:
Alarms:
Switches:
SURGE / NOISE SUPPRESSION
AC surge suppression:
AC suppression response time:
EMI / RFI AC noise suppression:
PHYSICAL
Shipping weight (lbs):
Shipping weight (kg):
Unit weight (lbs):
Unit weight (kg):
Unit Dimensions (HWD/in):
regulated to 60Hz +/-0.5Hz
8 NEMA 5-15R
on demand of locked network devices. Configurable via PowerAlert software to automatically
switch off optional loads, like monitors, to increase available runtime for servers and other
critical devices.
Resettable circuit breaker
12A / 1073 watts
NEMA 5-15P
10 ft., 14 gauge
15A 120V
12 minutes (1500VA), 57 minutes with 1 BP48V242U
30 minutes (750VA), 117 minutes with 1 BP48V242U
48 VDC
3-6 years, depending on usage
2-4 hours to 90%
Supports extended runtime with optional external battery packs BP48V242U (limit 1) and
BP48V60RT3U (multi-pack compatible)
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120V
nominal output, without using battery power, during brownouts to 79V and overvoltages to
147V
Input voltages between 128 and 147VAC are reduced by 12%
Input voltages between 105 and 127VAC are passed on to connected equipment unchanged
Input voltages between 95 and 104VAC are boosted by 12%
Input voltages between 79 and 94VAC are boosted by 24%
5 front panel LEDs - Green POWER LED, Green VOLTAGE CORRECTION LED, 3 color
BATTERY CHARGE LED, 3 color OUTPUT LOAD LEVEL LED, red BATTERY WARNING
LED.
3 function audible alarm indicates power failure conditions (4 short beeps every 10 seconds),
overload (continuous short beeps) and low battery (continuous tone)
Yes, includes 2 front panel mounted push-button switches for system enable, self-test and
alarm cancel functions
Conforms to IEEE 587 / ANSI C62.41 specifications
Instantaneous
Yes
62.2
28.2
52
23.6
3.5 x 17.5 x 16.5

Related parts for SMART1500RMXL2UA