APS2448UL Tripp Lite, APS2448UL Datasheet - Page 2

INVERTER 2400W 48VDC OR 120VAC

APS2448UL

Manufacturer Part Number
APS2448UL
Description
INVERTER 2400W 48VDC OR 120VAC
Manufacturer
Tripp Lite
Series
PowerVerter® APSr
Type
Inverter, UPSr
Datasheet

Specifications of APS2448UL

Voltage - Output
120VAC
Voltage - Input
48VDC, 120VAC
Ac Outlets
Hardwire
Connector - Ac Output
None (Hardwire)
Connector - Voltage Input
Terminals, Junction Box
Power - Output Continuous
2400W
Power - Output Surge
4800W
Remote Capability
Yes
Region Utilized
Internationally
Size
16.75" L x 8.50" W x 7.25" H (425.6mm x 215.9mm x 184.1mm)
Features
Auto Power Transfer for UPS Mode, Battery Charger
Weight
39 lbs (17.7kg)
Voltage - Input Connector
Terminals, Junction Box
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Ac Output Connector
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Specifications
OVERVIEW
Intended
Application
OUTPUT
Frequency
compatibility
Continuous output
capacity (watts)
Peak output
capacity (watts)
Output nominal
voltage
Output voltage
regulation
Output frequency
regulation
Overload
protection
Outlet quantity /
type
INPUT
Floating 48VDC ground offers compatibility with positive or negative grounded DC systems, including 48V telco applications.
8 millisecond automatic transfer between line and battery power supports UPS protection during blackouts and voltage fluctuations for
nearly all computer and networking applications
2400 watts continuous AC output in inverter mode, 2400 watts continuous AC output in AC mode
Double Boost™ inverter output supports momentary startup loads up to 200% of the continuous rating for up to 10 seconds
OverPower™ inverter output supports longer duration overloads to 150% for 1-60 minutes under ideal battery and temperature conditions.
(For best results, utilize OverPower usage for as short of a duration as possible, ensure battery bank and cabling is able to provide full
nominal DC voltage under load and allow inverter/charger to fully cool before and after OverPower usage.)
3 stage, 15 amp battery charger with adjustable settings for wet/gel battery types offers fast, reliable battery recharging
Protected hardwire bolt-down input lugs safely accept heavy gauge input wiring from attached battery bank
Protected hardwire output passes 120V line power or inverter output through to connected equipment
Reliability enhanced large-transformer design tested to UL (USA) and CSA (Canada) standards
Moisture-resistant construction enables vehicular or marine operation in high humidity environments
3 position operating mode switch supports "AUTO" mode to enable automatic transfer between DC and AC modes, CHARGE-ONLY to
maintain a full battery charge when AC is present without auto transfer and SYSTEM OFF settings
Set of six front panel LEDs display AC/DC operational modes, overload status, DC voltage level, shutdown status and system fault status
Set of 4 configuration dipswitches support wet/gel battery charging profiles, adjustable 135/145V high voltage auto transfer during
overvoltages and selectable 75/85/95/105V AC low voltage auto transfer during brownouts
Set of 4 additional configuration dipswitches support 4 levels of charger limiting relative to output load size, a battery equalization program
and battery charger on / off settings
Resettable 15A charger AC input breaker and resettable 20A AC output breaker and automatic 2 speed cooling fan protect the inverter from
load and temperature related failures
Grounding lug properly connects the inverter/charger system to earth ground or vehicle grounding system
Automatic overload and thermal shutoff safely turns off inverter as excessive loads or overheating conditions develop
Front panel remote control connector enables remote off/on switching (requires APSRM4 switch accessory). Optional APSRM4 accessory
also includes user configurable jacks to support inverter shutoff or startup as a vehicle ignition is engaged
Load sensing control dial enables adjustable load threshold required to automatically turn the inverter on and off in DC mode as load
conditions change
Emergency Home Power (Sump Pumps, Furnice Motors, Lighting, Computers & Radio's)
60 Hz
2400
4800
120V
LINE POWER (AC): Maintains 120V nominal sine wave output from line power source. INVERTER POWER (AC):
Maintains PWM sine wave output voltage of 120 V AC (+/-5%).
60 Hz (+/- 0.3 Hz)
Includes 15A input breaker dedicated to the charging system and 20A output breaker for AC output loads.
Hardwire

Related parts for APS2448UL