ADT7476ARQZ ON Semiconductor, ADT7476ARQZ Datasheet - Page 55

IC REMOTE THERMAL CTRLR 24QSOP

ADT7476ARQZ

Manufacturer Part Number
ADT7476ARQZ
Description
IC REMOTE THERMAL CTRLR 24QSOP
Manufacturer
ON Semiconductor
Series
dBCool®r
Datasheet

Specifications of ADT7476ARQZ

Function
Fan Control, Temp Monitor
Topology
ADC, Comparator, Fan Speed Counter, Multiplexer, Register Bank
Sensor Type
External & Internal
Sensing Temperature
-40°C ~ 125°C, External Sensor
Output Type
SMBus™
Output Alarm
No
Output Fan
Yes
Voltage - Supply
3 V ~ 3.6 V
Operating Temperature
-40°C ~ 125°C
Mounting Type
Surface Mount
Package / Case
24-QSOP
Full Temp Accuracy
+/- 0.5 C
Digital Output - Bus Interface
Serial (3-Wire, 4-Wire)
Maximum Operating Temperature
+ 125 C
Minimum Operating Temperature
- 40 C
Lead Free Status / RoHS Status
Lead free / RoHS Compliant

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
ADT7476ARQZ
Manufacturer:
ADI/亚德诺
Quantity:
20 000
Part Number:
ADT7476ARQZ-REEL
Manufacturer:
ON/安森美
Quantity:
20 000
Company:
Part Number:
ADT7476ARQZ-REEL
Quantity:
50
1. These registers become read−only when the Configuration Register 1 lock bit is set to 1. Any subsequent attempts to write to these registers fail.
Table 30. PWM Configuration Registers
Bit No.
[2:0]
[7:5]
Register Address
[3]
[4]
0x5C
0x5D
0x5E
Name
BHVR
SPIN
RES
INV
R/W (Note 1)
R/W
R/W
R/W
R/W
R/W
R/W
R/W
N/A
These bits control the startup timeout for PWMx. The PWM output stays high until two valid
TACH rising edges are seen from the fan. If there is not a valid TACH signal during the fan
TACH measurement directly after the fan startup timeout period, the TACH measurement
reads 0xFFFF and Interrupt Status Register 2 reflects the fan fault. If the TACH minimum
high and low bytes contain 0xFFFF or 0x0000, the Interrupt Status Register 2 bit is not set,
even if the fan has not started.
000 = No startup timeout
001 = 100 ms
010 = 250 ms (default)
011 = 400 ms
100 = 667 ms
101 = 1 sec
110 = 2 sec
111 = 4 sec
Reserved. Do not write to this bit.
This bit inverts the PWM output. The default is 0, which corresponds to a logic high output for
100% duty cycle. Setting this bit to 1 inverts the PWM output, so 100% duty cycle
corresponds to a logic low output.
These bits assign each fan to a particular temperature sensor for localized cooling.
000 = Remote 1 temperature controls PWMx (automatic fan control mode).
001 = Local temperature controls PWMx (automatic fan control mode).
010 = Remote 2 temperature controls PWMx (automatic fan control mode).
011 = PWMx runs full speed (default).
100 = PWMx disabled.
101 = Fastest speed calculated by local and Remote 2 temperature controls PWMx.
110 = Fastest speed calculated by all three temperature channel controls PWMx.
111 = Manual mode. PWM current duty cycle registers (0x30 to 0x32) become writable.
http://onsemi.com
PWM1 configuration
PWM2 configuration
PWM3 configuration
Description
55
Description
Power−On Default
0x62
0x62
0x62