ASI4UC-G1-SR-7 ZMDI, ASI4UC-G1-SR-7 Datasheet - Page 44

no-image

ASI4UC-G1-SR-7

Manufacturer Part Number
ASI4UC-G1-SR-7
Description
Interface - Specialized ASI
Manufacturer
ZMDI
Datasheet

Specifications of ASI4UC-G1-SR-7

Product Category
Interface - Specialized
Rohs
yes
Product Type
Actuator Sensor Interface IC
Operating Supply Voltage
16 V to 33.1 V
Supply Current
6 mA
Maximum Power Dissipation
850 mW
Maximum Operating Temperature
+ 85 C
Mounting Style
SMD/SMT
Package / Case
SSOP-28
Minimum Operating Temperature
- 25 C
Figure 16: Flowchart - Data_Exchange_Disable
3.7.7.
In Master-, Repeater- and Monitor Mode the data input and data output ports are differently configured than in
Slave Mode. Following control signals are provided at the data input port in Master-, Repeater- and Monitor
Mode:
Table 24: Control signal inputs in Master-, Repeater- and Monitor Mode
Note: The complemented definition was chosen to retain backward compatibility to A²SI based AS-i Master
designs.
The Data Output Port is exclusively used in Monitor Mode to provide additional UART error signals. The
signals are defined active low and will be set immediately after a telegram error was detected. They become
reset at the beginning of the next telegram. Following signals are available:
Table 25: Error signal outputs in Monitor Mode
3.7.8.
Besides of its standard output function the Data Strobe Pin serves as external reset input for all operational
modes of the IC. Pulling the DSR pin LOW for more than a minimum reset time generates an unconditioned
reset of the IC, which is immediately followed by a re-initialization of the IC (E²PROM read out).
Further information on the IC reset behavior, especially in regard to the signal timing, can be found at chapter
3.11 IC Reset.
Data Sheet
January 30, 2012
Data Input Port
DI0
DI1
DI2
DI3
Data Port Output
DO0
DO1
DO2
DO3
ASI4U / ASI4U-E
Spec. 3.0 Com
Filter_Enable
Sync_Enable
Safety_Mode
Master-, Repeater-, Monitor Mode
Special function of DSR
© 2012 Zentrum Mikroelektronik Dresden AG — Rev. 2.1
All rights reserved. The material contained herein may not be reproduced, adapted, merged, translated, stored, or used without
the prior written consent of the copyright owner. The information furnished in this publication is PRELIMINARY and subject to
changes without notice.
pliant Universal AS-I IC
Signal Name
invert_ird_a
invert_ird_b
invert_led1_a
invert_led1_b
UART Error Signal Description
plscod_err
no_info_err
parb_err
ird_man_err
>=1
Description
If the signals invert_ird_a and invert_ird_b are unequal, the IRD
input signal is inverted before further processing. See Table 13.
If the signals invert_led1_a and invert_led1_b are unequal, the LED1
output signal is inverted after processing. See Table 28.
Pulse Code Error
No Information Error
Length Error
Parity Bit Error
Man-II-Code Error at
IRD input
&
Data_Exchange_Disable
Indicates faulty AS-i pulses. This is a
disjunction of alternation error, start bit error,
end bit error
The output signal is a disjunction of
No_Information_Error and Length_Error as
defined in the Complete Spec 3.0.
The Monitor Mode does not distinguish
between synchronized and not synchronized
UART Mode. There is always only one bit
time supervised after the end of a telegram.
Received parity bit does not match the check
sum calculated by the UART
Signal at IRD input violates MAN-II-Coding
rules
44 of 63

Related parts for ASI4UC-G1-SR-7