Hydraulic Elevators
Hydraulic Elevators need battery backup to help prevent
stranding passengers. To keep the elevator from moving
when it’s been manually shut down for maintenance, the
NEC
disconnecting means through an auxillary contact.
However, an unintended consequence can be passengers
getting stranded because of devices that open
automatically (circuit breakers and disconnects utilizing a
The Power Module™ is the best choice for design
engineers or electrical contractors that need to meet these
requirements, Codes and standards:
With the Power Module You Get:
Notes: A lways follow established safety practices when wo rking
on a electrically live equipment.
Allows Elevator Shutdown – NEC
Auxiliary Contact (Hydraulic Elevator) – NEC
“override” for troubleshooting
Scenario
Power failure
Fire in shaft or
machine room
Disconnect manually
opened
Fault on loadside of
disconnect
Elevator Shutdown – ANSI/ASME A17.1 Rule 102.2(c)(3)
Shunt Trip Voltage Monitoring – NFPA 72-1999 3-9.4.4
Integrity Monitoring – NFPA 72-1999 3-9.2.1
Selective Coordination – NEC
Orderly Shutdown – NEC
Shunt trip capability
Selective coordination
Fire safety signal interface
Shunt trip voltage monitoring
Component protection via Low-Peak
UL 98 Listed for 200kA short-circuit current rating
Lockable in the open position with three lock capability
Optional key-test switch and optional pilot light for easy
inspection
No annual calibration or testing of overcurrent protection
required
Padlockable for service work safety and open door
Disconnects
Power Module™ — all-in-one elevator disconnect
®
requires battery backup be connected to the elevator
For product data sheets, visit www.cooperbussmann.com/products/datasheet.asp
Lowering
Required
Battery
®
Yes
Yes
240.12
No
No
®
620.62
®
620.51
®
Reason
Need to lower elevator to allow passengers to exit
Recall is initiated by smoke detector and lowers elevator to
a safe floor. Battery not needed
Worker to perform maintenance. Elevator must remain
stationary to prevent injury
Need to lower elevator to allow passengers to exit
Class J fuses
®
620.91(C)
molded case switch with a trailing fuse block) will operate
with a fault on their loadside. That operation also disables
the battery backup and strands passengers. That’s why the
Power Module has a non-automatic fusible shunt trip
switch. If the Power Module has a fault on its loadside, the
fuses open and the battery stays enabled. Thus the Power
Module ensures that battery power is enabled when the
passengers need it to exit, and disabled to allow safe main-
tenance of the elevator and hoistway.
Power Module™ Panel (PMP)
Offered By
Module™
Power
Yes
Yes
Yes
Yes
Other Elevator
Disconnects
Offered By
Yes
Yes
Yes
No