G6D-F4B OMRON [Omron Electronics LLC], G6D-F4B Datasheet - Page 6

no-image

G6D-F4B

Manufacturer Part Number
G6D-F4B
Description
Easy-to-use, Space-saving Terminal Relay with Four-point Output
Manufacturer
OMRON [Omron Electronics LLC]
Datasheet

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
G6D-F4B-DC24V
Manufacturer:
OMRON
Quantity:
1 000
G6D-F4B/G3DZ-F4B
Precautions
Wiring
Be sure to turn OFF the power when wiring the Unit and do not touch
the charged terminals of the Unit. Otherwise, an electric shock may
result.
Do not apply overvoltage to the input terminals. Otherwise, the Unit
may malfunction or burn.
Relay Models
Do not connect the Unit to loads exceeding the rated switching ca-
pacity (switching voltage or current). Otherwise, faulty insulation,
contact weld, or faulty contact of Relays, or damage to Relays may
result, or the Relays may malfunction or burn.
The life of Relays varies with the switching condition. Test the
Relays under the actual operating conditions before using the
Relays within the permissible switching frequency. The use of dete-
riorated Relays may result in the faulty insulation of the Relays or
cause the Relays to burn.
Do not use the Unit in locations with inflammable gas. Otherwise, a
fire or explosion due to the heat of the Relays or sparks from the
Relays may result when they are switched.
SSR Output (Power MOS FET Relay Model)
Do not connect the Unit to loads consuming a total current exceed-
ing the rated output current of the Unit. Otherwise, the output ele-
ment of the Unit may be damaged and a short or open-circuit mal-
function may result.
If the Unit is connected to a DC inductive load, connect a diode to the
Unit to protect the Unit from counter-electromotive voltage, other-
wise the counter-electromotive voltage may damage the output ele-
ment and a short or open-circuit malfunction may result.
Mounting
When mounting two or more Units, reduce the current and ON duty
and provide an appropriate distance between the Units so that the
ambient temperature will not exceed 55 C.
Relay Replacement
Use the Relay Removal Tool provided with the Unit to dismount a
Relay.
Be sure to turn OFF the power to the Unit before replacing a Relay.
When mounting a Relay, insert the Relay vertically so that the relay
terminals will come in contact with the socket contact pins properly.
Do not mount Relays that are different to one another in voltage.
Wiring
Pay utmost attention not to make mistakes with the polarity of the
input terminals.
6
Correct Use
Coil Voltage
Make sure not to impose voltage exceeding the permissible voltage
on the coil continuously.
Do not connect any inductive load in parallel to the coil input as
shown in the following example or power supply with a surge volt-
age. Otherwise, the surge absorption diode will be damaged.
Do Not Use the Following Circuit
Handling
Do not drop, shock, or vibrate the Unit excessively. Otherwise, dam-
age to the Unit may result or the Unit may malfunction.
Make sure that all the Relays are properly mounted before use.
Screw Tightening Torque
Tighten each terminal screw to a torque of 0.78 to 1.18N m.
Tighten each mounting screw to a torque of 0.59 to 0.98 N m.
Installation Environment
Do not install the Unit in the following locations. Otherwise, damage
to the Unit may result or the Unit may malfunction.
Locations with direct sunlight.
Locations with an ambient temperature range not within –25 C to
55 C.
Locations with rapid temperature changes resulting in condensa-
tion or locations with relative humidity ranges not within 45% to
85%.
Locations with corrosive or inflammable gas.
Locations with excessive dust, salinity, or metal powder.
Locations with vibration or shock affecting the Unit.
Locations with water, oil, or chemical sprayed on the Unit.
Disassembly, Repair, and Modification
Do not disassemble, repair, or modify the Unit. Otherwise, an elec-
tric shock may result or the Unit may malfunction.
Inductive load
G6D coil
G6D-F4B/G3DZ-F4B
Coil surge
absorption
diode

Related parts for G6D-F4B