FC-10C GAMEWELL-FCI [Gamewell-FCI by Honeywell], FC-10C Datasheet

no-image

FC-10C

Manufacturer Part Number
FC-10C
Description
Ten zone control communicator
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
Description
The FC-10C Fire Alarm Control panel is a proven, versa-
tile, ten-zone modular control with integral communicator
and remote-site upload/download capability. It meets the
requirements of NFPA Standard 72 for Central Station,
Protected Premises, and Remote (DACT) Supervising
Station Fire Alarm Systems. It is Listed to UL Standard
864, inherently power limited and meets all UL transient
immunity requirements.
The integral communicator includes a wide range of se-
lectable transmission formats to communicate to virtually
all central stations. Other features of the communicator
are: A line-active indicator for each of two phone lines,
“Kiss-Off” signal LED, dual “low telephone voltage detect”
circuitry, programmable event codes per format and se-
lectable/deselectable transmission of up to 100 events.
Multiple security techniques allow uploading or download-
ing within one minute without affecting normal fire panel
functions. Key system information that can be uploaded
are: Current System Status, History, Walk Test Files and
System Programming.
An integral voltmeter allows voltage measurements for
Zone, AC line, NAC1, NAC2, resettable power and bat-
tery.
Housed in a red steel enclosure, the surface mounted
unit, (trim ring optional) provides space for two (2) B-7R
batteries.
The many features of the FC-10C control provide a cost
effective approach to systems design, and allow a great
degree of flexibility in one enclosure. Many of these fea-
tures include two (2) notification appliance circuits
(expandable to four) with output expandable from 3.0 to
6.0 amps total. Class A operation is possible with optional
modules. Fully programmable via integral keypad, the
notification appliance circuits may be programmed Si-
lenceable, Non-silenceable, Auto-silence (program 5 to 30
minutes) and Silence Inhibit (60 seconds).
Initiating zones may be programmed for process monitor-
ing via latching or non-latching contact closure and can be
used to monitor high-low temperature, loss of air flow,
water level, gas detection, open/close, refrigeration and
non-fire related tamper functions.
Also programmable are Alarm Presignal Timer, Alarm
Verification Timer and Optional Trouble Reminder.
©
2006 Gamewell-FCI. All rights reserved.
Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
12 Clintonville Road, Northford, CT 06472 - Tel: 203-484-7161 - Fax: 203-484-7118
www.gamewell-fci.com
GAMEWELL-FCI
Features
• Inherently power-limited.
• Integral digital communicator.
• Fifteen (15) selectable transmission formats.
• Up to 100 transmitted events/messages.
• Fire Drill Function.
• Integral voltmeter.
• Fully programmable via integral keypad.
• Auto-reset supervisory operation.
• Temporal pattern output per ANSI S3.41.
• Single person walk test with 256 event walk test
• Alarm verification.
• Real-time clock/calendar.
• 256-Event History with time and date stamp, stored in
• Zone disable feature via software.
• Two (2) fully programmable Form “A” relay contact
• Programmable trouble reminder.
• Surface mount technology.
• Ground start module (optional).
• Contact-by-Zone module (optional).
• Serial annunciator output (optional).
• Printer interface for on or off-line printing (optional)
memory.
output.
permanent memory.
Conventional Fire Alarm Control
An ISO 9000-2000 Company
TEN ZONE PANEL
FC-10C
9020-0459 Rev. G page 1 of 2
FC-10C

Related parts for FC-10C

FC-10C Summary of contents

Page 1

... Description The FC-10C Fire Alarm Control panel is a proven, versa- tile, ten-zone modular control with integral communicator and remote-site upload/download capability. It meets the requirements of NFPA Standard 72 for Central Station, Protected Premises, and Remote (DACT) Supervising Station Fire Alarm Systems Listed to UL Standard 864, inherently power limited and meets all UL transient immunity requirements ...

Page 2

... Backbox 16 7/8" 1/2" 1/2" D (42.93 x 36. 11.43 cm) Trim Ring 20 1/8" 5/8" W (50.85 x 44.75 cm) UL Listed Receivers compatible with FC-10C: • Ademoco 685 • Osborne Hoffman Models • Silent Knight 9000 • Radionics 6000/6500 • ITI-CS-4000 • Sescoa 3000R • ...

Related keywords