NICFP-BP-4 NI [National Instruments Corporation], NICFP-BP-4 Datasheet - Page 3

no-image

NICFP-BP-4

Manufacturer Part Number
NICFP-BP-4
Description
Digital Input Modules for Compact FieldPoint
Manufacturer
NI [National Instruments Corporation]
Datasheet
Digital Input Modules for Compact FieldPoint
Specifications
Typical for -40 to 70 °C unless otherwise noted.
Digital Input Channels
cFP-DI-300, cFP-DI-330 .......................................................... 8
cFP-DI-301.............................................................................. 16
cFP-DI-304.............................................................................. 32
Input Characteristics
Input impedance
Input current limiting cFP-DI-330........................................... 1.5 mA
Input Voltages
cFP-DI-300, cFP-DI-301, cFP-DI-304....................................... 0 to 30 VDC
cFP-DI-330.............................................................................. 0 to 250 VDC or 0 to 250 VAC (50/60 Hz AC) or 0 to 250 VAC (1 kHz AC)
Digital Logic Levels
Hysteresis (cFP-DI-304)
Input voltage .......................................................................... 2 V min
Input current........................................................................... 60 µA min
Isolation Voltage
cFP-DI-30x
cFP-DI-330
Transient overvoltage ............................................................ 2,300 V
Physical Characteristics
LED indicators
Dimensions ........................................................................... 127.0 by 65.9 by 23.9 mm (5.00 by 2.60 by 0.94 in.)
Weight
Input Voltage (V)
Input Current (µA)
cFP-DI-300, cFP-DI-301...................................................... 5 kΩ
cFP-DI-304.......................................................................... 30 kΩ
Channel-to-ground
Channel-to-backplane
Channel-to-channel ........................................................... None
Maximum isolation voltage............................................... 250 V
Power (green) .................................................................... Power on and self-test passed
Ready (green)..................................................................... Module configured and ready
<0..31>, <0..15>, or <0..7> (green) ....................................... Input state of each channel
cFP-DI-300/301 .................................................................. 100 g (3.6 oz)
cFP-DI-330.......................................................................... 103 g (3.7 oz)
cFP-DI-304.......................................................................... 193 g (6.81 oz)
Continuous .................................................................... 250 V
Withstand...................................................................... 2,300 V
Continuous .................................................................... 250 V
Withstand...................................................................... 2,300 V
OFF State ON State OFF State ON State OFF State ON State OFF State
≤1000
<5
cFP-DI-300
≥3000
>15
≤1000
<5
cFP-DI-301
≥3000
>15
≤150
≤5
cFP-DI-304
≥330
≥10
rms
rms
rms
rms
rms
rms
, Installation Category II
≤1 VDC, ≤1
, 5 s max
, 5 s max
VAC
≥4 VDC, ≥15 VAC (50/60 Hz AC),
cFP-DI-330
≥3 VAC (1 kHz AC)
ON State
BUY ONLINE at ni.com or CALL 800 813 3693 (U.S.)
3