BAT-12180 GAMEWELL-FCI [Gamewell-FCI by Honeywell], BAT-12180 Datasheet - Page 2

no-image

BAT-12180

Manufacturer Part Number
BAT-12180
Description
Audio Command Center Voice Evacuation Control Panel
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
Controls and Indicators
1. Power On (green).
2. System Trouble (yellow).
3. Message Generator Trouble (yellow).
4. Tone Generator Trouble (yellow).
5. Microphone Trouble (yellow).
6. Record/Playback (green).
7. Zone 1 (green = Active, yellow = Manual Deactivation).
8. Zone 2 (green = Active, yellow = Manual Deactivation).
Other System LEDs: Battery Trouble, Charger Trouble, Ground Fault,
Speaker Circuit Trouble, and Amplifier Supervisory.
Ordering Information
Page 2 of 4
ACC-AAM25
FC-RM
BAT-1270
BAT-12120
BAT-12180
GWACC
FC-XRM70
FC-LPS
25 watt, 25 V
Panel (VECP) with integral commercial microphone, digital
message generator, and single-/dual-channel Class A or
Class B speaker circuit.
Optional 25 watt, 25 V
single Class A or Class B speaker circuit.
Optional 70.7 V
amplifier, consult factory for availability).
Optional Remote Microphone, includes backbox (only one
FC-RM per system).
Optional Local Playback Speaker.
Battery, 12 volt, 7.0 AH (two required).
Battery, 12 volt, 12.0 AH (two required).
Battery, 12 volt, 18.0 AH (two required).
RMS
RMS
, emergency Voice Evacuation Control
Converter Module (one required per
RMS
Audio Amplifier Module with
GWACC CS-2504 09/01/06
Module Features
ACC-AAM25
• 25 watt, 25 V
• Field-programmable for system
• Provides single Class A or Class B
• Utilizes plug-in-style terminal blocks for
• Fully supervised and power-limited.
• Diagnostic LEDs include: yellow
FC-XRM70
• Converts 25 V
• Plugs directly on ACC-AAM25
FC-LPS
• Provides local digital message playback
Specifications
Electrical specifications
Cabinet dimensions
module.
expansion to 50 watts (providing dual
25-watt speaker circuits) or as a
backup to the primary 25-watt amplifier
where required.
speaker circuit.
ease of service and maintenance.
“trouble” LED (cable fault, 70 V
fault, amp fault) and green “amp
functional” LED.
V
module(s), allowing independent
conversion to 70.7 V
for user review of field-recorded
custom messages.
Command input circuits (CMD1
and CMD2):
Trigger input voltage 10.5 — 29 VDC.
NOTE: When programmed for
reverse-polarity activation.
Trouble contact rating: 2.0 A at 30
VDC (resistive), 0.6 A @ 125 VAC
(resistive).
Auxiliary power output: Specific
application power 24 V, 35 mA.
Primary (AC) power: 1.6 A maximum
@ 120 VAC, 50/60 Hz.
Secondary power (battery)
charging circuit:
• Supports lead-acid batteries only.
• Float-charge voltage: 27.6 V.
• Maximum charge current: 800 mA.
• Maximum battery charging capacity:
18 AH.
Door: 26.174" (66.482 cm) high x
15.780" (40.081 cm) wide x 1.125"
(2.858 cm) deep. Backbox: 26.0"
(66.040 cm) high x 15.5" (39.370 cm)
wide x 4.75" (12.065 cm) deep, depth
includes door.
Standards and Codes
The GWACC complies with the
following standards: NFPA 72 National
Fire Alarm Code; NFPA 101 Life Safety
Code; UL 864 Standard for Control
Units for Fire Alarm Systems; and UL
1711 Standard for Amplifiers for Fire
Alarm Systems.
RMS
for retrofit applications.
RMS
RMS
audio outputs to 70.7
audio amplifier
RMS
.
RMS

Related parts for BAT-12180