BAT-12120 GAMEWELL-FCI [Gamewell-FCI by Honeywell], BAT-12120 Datasheet - Page 2

no-image

BAT-12120

Manufacturer Part Number
BAT-12120
Description
NAC Expander/Power Supply
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
Engineer’s Specifications
The Fire Alarm System shall be designed with remotely
located Notification Appliance Circuit (NAC) Expander/
Power Supplies for the support of notification appliances.
The remote Power Supplies shall be fully supervised and
shall provide 8.0 Amps. of notification appliance power and
1.5 Amps. of auxiliary power output. The NAC Extender
Panel shall be able to select strobe synchronization proto-
col via an internal dip switch. There shall be five selectable
protocols available. The NAC Extender Panel shall syn-
chronize all outputs simultaneously. The NAC Extender
Panel shall be able to use existing notification appliance
circuit’s end-of-line resistors in the range of 2K – 25K ohms
for retrofit applications. The internal battery charging circuit
shall charge up to 26 AH batteries. The NAC Expander/
Power Supply shall be a Gamewell-FCI FireForce 8.
Options
31081
SCE-95 mounting plate provides a means to install two (2)
SCE-95 modules. The addition of SCE-95s provides a
means to run on FF8 outputs via a panel command on an
SLC. The 31081 mounts over the main PCB and is hinged
for access to FF8 terminal.
FF8-MP
Multipack FF8 option provides a means to place up to four
(4) FF8s or 31085s (XP95 device mounting plates) in a sin-
gle lockable enclosure. UL approved.
31076
Class A adaptor converts the four (4) Class B outputs to
four (4) Class A outputs.
Specifications
Primary Input Power: 120 VAC, 60 Hz, 3.0 A
Secondary Power:
Battery Charging
Capacity:
Battery Space:
Total Output Power:
Standby Current:
Auxiliary Power
Output:
NAC Output Ratings: 24 VDC fully regulated, 3.0 A
End-of-Line Resistor
Range:
Common Trouble
Relay, AC Fail Relay: 2.0 A/28 VDC or 120 VAC
CS-2282 Rev. a page 2 of 2
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
or 220 V, 1.5 A; jumper selectable
24-volt operation: two 7 – 24 AH
batteries
Up to 26 AH batteries
Up to two 12 AH batteries maxi-
mum inside the FF8 cabinet.
Larger batteries require a separate
battery cabinet
8.0 A maximum
0.030 A
0.15 A under all conditions
1.5 A, if load is removed during
operation (external relay or AC
Fail relay use required).
maximum per circuit (8.0 A total)
2K to 25K, 1/2 watt
www.gamewell-fci.com
GAMEWELL-FCI
Specifications (Continued)
Input Control Circuit: 16 – 30 VDC @ 5 mA minimum
Temperature Rating: 32°F to 120°F (0°C to 49°C)
Relative Humidity:
Dimensions:
Steady
Steady
Steady
Sync
Ordering Information
Model
FF8
FF8-MP
FF8-CM
31076
31085
BAT-1270
BAT-12120
31081
INPUT
Field Selectable NAC Signaling
Sync
Description
Temporal
Steady - SYNC
Steady with Noise Eliminated
24 VDC, 8.0 Amp., fire alarm NAC
expander/ power supply with integral
battery charger
Multipack cabinet with one FF8 and
space for up to three additional FF8-CMs
or 31085s (See Options Section).
Chassis assembly version of FF8, for
mounting in FF8-MP spaces
Class A adaptor, converts signal circuits
to Class A wiring (See Options Section).
Mounting plate for placing up to two
SCE-95 modules into the FF8
(FF8 and FF8-MP compatible, See
Options Section).
Mounting plate for placing XP95 devices
into the FF8-MP; includes standoffs for
eight devices
Battery, 12 VDC, 7 AH
(two required for 24 V operation)
Battery, 12 VDC, 12 AH
(two required for 24 V operation)
10 - 93%, non-condensing
FF8 Cabinet:
18.0" H x 12.5" W x 4.5" D
(45.72 H x 31.75 W x 11.43 D cm)
FF8-MP Cabinet:
37.2" H x 24.0" W x 6.0" D
(94.49 H x 60.96 W x 15.24 D cm)
OUTPUT (Follows Input)