P1224MCK GAMEWELL-FCI [Gamewell-FCI by Honeywell], P1224MCK Datasheet - Page 3

no-image

P1224MCK

Manufacturer Part Number
P1224MCK
Description
SELECTABLE OUTPUT STROBES AND HORNS
Manufacturer
GAMEWELL-FCI [Gamewell-FCI by Honeywell]
Datasheet
Specifications
Walk Test
SpectrAlert horn/strobe and horn only operate on
“walk tests” with time durations of 4 seconds
or greater
Input terminals
12 to 18 AWG
Dimensions
Strobe and horn/strobe with universal plate
5” x 5
Strobe and horn/strobe with small
footprint plate
3
Horn with universal mounting plate
5” x 5
Horn without mounting plate
2
Weight, horn only
7.2 0z.
Weight, strobe and horn/strobe
8.8 oz.
Ordering Information
Description
Horn/Strobes
Strobes
*NOTE: Strobes available for 12 V operation in 15 and 15/75 cd only
Accessories
Sync. Circuit Module MDL
Small Mtg Plate for
Single Gang
Surf. Mt. Back
box skirt
Universal Mtg. Plate D-MP
(replacement)
Specifications are provided for information only, and are not intended to be used for installation purposes and are believed to be accurate.
However, no responsibility is assumed by Fire Control Instruments for their use. Specifications subject to change without notice.
15
3
/
8
/
16
” x 5
” x 5
5
5
16 Southwest Park, Westwood, MA 02090 USA • Tel: 781-471-3000 • Fax: 781-471-3099 • www.firecontrolinstruments.com
/
/
8
8
” x 2
” x 1
5
/
5
8
/
” x 2
16
15
5
” x 1
/
/
16
16
5
/
5
16
/
P1224M
SMP
S1224MC S1224MCW
BBS
16
Red
SMPW
D-MPW
MDLW
BBSW
P1224MCW
White
S1224MCK 12/24
P1224MCK 12/24
WP
12/24
NA
NA
NA
FIRE CONTROL INSTRUMENTS
A Honeywell Company
Voltage
NA
NA
NA
NA
Candela
15, 15/75, 30, 75, 110*
15, 15/75, 30, 75, 110*
Selectable:
Selectable:
Strobe and Horn/Strobe
Mounting
4” x 4”x 1
standard boxes
Indoor operating temperature
32°F to 120°F (0°C to 49°C)
Maximum humidity
95% as tested per UL464
Weatherproof (horn and horn/strobe)
Operating temperature
32°F to 150°F (0°C to 66°C)
(Weatherproof strobe only)
-40°F to 158°F (-40°C to 70°C)
Voltages
12 or 24VDC and FWR unfiltered
Operating Voltage Range*
12V: 8-17.5 V; 24V: 16-33 V
Operating Voltage Range
(with Sync•Circuit module MDL)
12V: 9-17.5 V; 24V: 17-33 V
*
voltage range; UL does test functional integrity to-20%
and +10% of manufacturer’s stated ranges.
These products should be operated within their rated
1
/
2
Selectable Output
” or 2” x 4” x 1
Avg.mA*
@Nom. VDC
-
-
10/11
NA
NA
NA
SpectrAlert
7
/
8
9020-0562/Ver. 1.2 / Page 3 of 3
© 2003 All Rights Reserved
Avg.mA*
@Nom. VDC
-
-
12/15
NA
NA
NA

Related parts for P1224MCK