Programming (Continued)
When the sensor head is inserted into the base, the
address is automatically relayed to the sensor. Changing
the sensor does not require additional programming since
the address remains on the XPert card located in the base.
All other sensor-specific programming is accomplished at
the FACP.
Engineer’s Specifications
The contractor shall furnish and install, where indicated on
the plans, analog addressable air duct smoke detectors.
The sensors shall be listed by Underwriter’s Laboratories
per UL 268A and UL-Listed as compatible with the Fire
Alarm Control Panel (FACP). The sensors shall operate at
air velocities from 300 to 4,000 feet (91.44 to 1219.20 m) per
minute. The smoke sensor shall contain an integral LED
that shall latch in when the unit goes into alarm, mounted at
a 30° slant to provide a wide viewing angle.
A manual reset/test switch shall be located on the front of
the device. The housing shall contain a sensor base which
will accept photoelectric or ionization heads. All wiring must
comply with local codes and regulations. The duct sensor
housing shall have a metal chassis with a clear plastic
cover and complete mechanical installation may be per-
formed without removal of the cover. The duct smoke
detector shall be the Gamewell-FCI model, XP95-ID(R) or
XP95-PD(R) analog addressable duct smoke detector.
Specifications
Ambient Temperature: 32° F to 120°F (0°C to 49°C)
Humidity:
Material:
Dimensions:
Maximum Net Weight: 4.0 lbs. (1.814 kg)
Mounting:
Radioactive Element: For Ionization versions only:
Sensitivity:
Air Velocity:
Pressure Differential: 0.01 to 1.2 inches (1.524 to 20.320
Standby Current:
Alarm LED Current:
Remote Alarm Output
Range:
CS-2049 Rev. a1 page 2 of 2
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
10% to 85% R.H
18 gauge steel backbox,
clear plastic cover
10.0" H x 8.25" W x 2.25" D
(25.4 H x 21.0 W x 5.7 D cm)
Template and necessary
hardware supplied
Americium 241 (0.9 microcuries)
Factory set (ion); or adjustable
via the IF600 control panel
(photoelectric)
300 to 4,000 feet per minute.
meters per second) of water
Photoelectric: 340 µA
Ionization:
Photoelectric: 4 mA
Ionization:
20 mA maximum; diode gated
280 µA
2 mA
www.gamewell-fci.com
GAMEWELL-FCI
Specifications (Continued)
Relay Versions Only:
Relay Contacts:
Relay Contact Ratings: 10 A @ 24 VDC resistive
Operating Voltage:
Current:
Ordering Information
Model
XP95-ID
XP95-PD
30203-01
XP95-IDR
XP95-PDR Four-wire air duct, photoelectric smoke
30203
30007-02
70896-02
70896-05
70896-10
XP95-I
XP95-P
72247
Description
Two-wire air duct, ionization smoke detector
24 VDC (RW-AAN)
Two-wire air duct, photoelectric smoke
detector 24 VDC (RW-AAP)
Remote LED alarm indicator (two VDCs);
used with XP95-PD and XP95-ID
Four-wire air duct, ionization smoke detector
24 VDC with relay (RW-ARN)
detector 24 VDC with relay (RW-ARP)
Remote LED alarm indicator (24 VDCs);
used with relay versions
Remote test station with alarm LED;
used with relay versions
Sampling tube, 2.5 feet (0.762 m)
Sampling tube, 5 feet (1.524 m)
Sampling tube, 10 feet (3.048 m)
Ionization sensor head (replacement)
Photoelectric sensor head (replacement)
Duct detector enclosure (WP-1)
(See Data Sheet CS-2308).
Two dry Form-C contacts
maximum
24 VDC
Standby current:
0.010 A @ 24 VDC
Alarm current:
0.055 A @ 24 VDC