co1224t System Sensor, co1224t Datasheet - Page 2

no-image

co1224t

Manufacturer Part Number
co1224t
Description
Manufacturer
System Sensor
Datasheet
CO1224T Carbon Monoxide Detector Specifications
Operation Modes
RealTest
Hush Feature:
Trouble Feature:
End-of-life Timer:
CO-PLATE:
Ordering Information
Architectural/Engineering Specifications
Carbon monoxide detector shall be a System Sensor model number CO1224T, listed to Underwriters Laboratories UL 2075 for Gas and Vapor Detectors and
Sensors. The detector shall be equipped with a sounder and a trouble relay. The detector’s base shall be able to mount to a single-gang electrical box or direct
(surface) mount to the wall or ceiling. Wiring connections shall be made by means of SEMS screws. The detector shall provide dual-color LED indication that
blinks to indicate normal standby, alarm, or end-of-life. When the sensor supervision is in a trouble condition, the detector shall send a trouble signal to the
panel. When the detector gives a trouble or end-of-life signal, the detector shall be replaced. The detector shall provide a means to test CO gas entry into the
CO sensing cell. The detector shall provide this with a test mode that accepts CO gas from a test agent and alarms immediately upon sensing CO entry.
Electrical Specifications
Operating Voltage
Audible Signal
Standby Current
Alarm Current
Alarm Contact Ratings
Trouble Contact Ratings
Physical Specifications
Size
Approximate Weight
Operating Temperature Range
Operating Humidity Range
Input Terminals
Mounting
Part No.
CO1224T
CO-PLATE
Operation Mode
Normal (standby)
Alarm
Feature:
Push and hold the Test/Hush button for
two seconds to enter RealTest mode. The
green LED will flash once every second to
indicate RealTest mode has started.
NOTE: Check with local codes and the AHJ to determine whether or not a functional gas test is desired for an installation.
T he System Sensor CO1224T carbon monoxide detector with RealTest
canned test agent.
P ushing the Test/Hush button will silence the sounder for 5 minutes (except in RealTest mode).
W hen the detector is in a trouble condition, it will send a trouble signal to the panel.
A fter the detector’s internal sensor has reached the end of its life, a trouble signal will be sent to the
panel. This will indicate that it is time to replace the detector. An electrochemical carbon monoxide
detector lifespan is approximately six years, and the detector must be replaced by the date marked
on the inside of the product.
S ystem Sensor also offers the CO-PLATE model to cover the footprint of previously installed carbon
monoxide detectors that require replacement.
Description
12/24 volt, 4-wire system-monitored carbon monoxide detector with RealTest
CO detector replacement plate to cover the footprint of previously installed detectors
1.
Green LED
Blink 1 per minute
12/24 VDC
85 dB in alarm
20 mA
40 mA (75 mA test)
0.5 A @ 30 VDC
0.5 A @ 30 VDC
Length: 5.1 inches, Width: 3.3 inches, Height: 1.3 inches
7 oz
32°F to 104° F (0°C to 40° C)
22 to 90% RH
14 to 22 AWG
Single-gang back box; surface mount to wall or ceiling
Phone: 800-SENSOR2 • Fax: 630-377-6495
3825 Ohio Avenue • St. Charles, IL 60174
Spray the canned CO agent into the
detector.
2.
Red LED
Blink in temp 4 pattern
can evaluate the functionality of the CO sensing cell using a
Technology
Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
Verify CO sensing at the control panel. The
detector will automatically exit RealTest
alarm mode after 20-60 seconds.
3.
Sounder
Sound in temp 4 pattern
A05-0437-001 • 8/10 • #2458
©2010 System Sensor.
CO-PLATE

Related parts for co1224t