General specifications
Signal type
Supply
Connection
Rated voltage
Ripple
Rated current
Power loss
Power consumption
Input
Connection
Rated values
Open circuit voltage/short-circuit current
Switching point/switching hysteresis
Line fault detection
Pulse/Pause ratio
Output
Connection
Output I
Output II
Contact loading
Minimum switch current
Energized/De-energized delay
Mechanical life
Transfer characteristics
Switching frequency
Electrical isolation
Input/Output
Input/power supply
Output/power supply
Output/Output
Indicators/settings
Labeling
Directive conformity
Electromagnetic compatibility
Low voltage
Conformity
Electromagnetic compatibility
Protection degree
Protection against electric shock
Ambient conditions
Ambient temperature
Mechanical specifications
Protection degree
Mass
Dimensions
General information
Supplementary information
Directive 2004/108/EC
Directive 2006/95/EC
Technical data
Digital input
Power Rail or terminals 9+, 10-
19 ... 30 V DC
≤ 10 %
≤ 30 mA
≤ 500 mW
≤ 500 mW
terminals 1+, 2-
acc. to EN 60947-5-6 (NAMUR)
approx. 10 V DC / approx. 8 mA
1.2 ... 2.1 mA / approx. 0.2 mA
breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
≥ 20 ms / ≥ 20 ms
output I: terminals 5, 6 ; output II: terminals 7, 8
signal ; relay
signal or error message ; relay
253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 30 V DC/2 A resistive load
2 mA / 24 V DC
≤ 20 ms / ≤ 20 ms
10
≤ 10 Hz
reinforced insulation according to IEC 61140, rated insulation voltage 300 V
reinforced insulation according to IEC 61140, rated insulation voltage 300 V
reinforced insulation according to IEC 61140, rated insulation voltage 300 V
reinforced insulation according to IEC 61140, rated insulation voltage 300 V
space for labeling at the front
EN 61326-1:2006
EN 50178:1997
NE 21
IEC 60529
IEC 61140
-20 ... 60 °C (-4 ... 140 °F)
IP20
approx. 100 g
12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in) , housing type A2