le12-25-yy technipower Systems, le12-25-yy Datasheet

no-image

le12-25-yy

Manufacturer Part Number
le12-25-yy
Description
10 Models ? Single Output ? Up To 400 Watts 1u Redundant Hot Swap Power Supplies
Manufacturer
technipower Systems
Datasheet
MODELS
300 Watt
400 Watt
Other ratings available on special order.
Replace the YY with the sum of the Option Codes at right.
290 Wissahickon Avenue, North Wales, PA 19454
Phone: 800.523.2332
Email: sales@deltroninc.com
Website: www.deltroninc.com
Output
1.8V @ 56A
2.5V @ 56A
3.3V @ 56A
5V @ 56A
12V @ 25A
24V @ 12.5A
48V @ 6.3A
Output
12V @ 33A
24V @ 16.7A
48V @ 8.3A
80% typical efficiency
1U high – SlimLine package
Hot Pluggable
Power Factor Corrected
EN 61000-3-2 compliant
Universal input
UL, CSA, TÜV (IEC, EN)
FCC, CISPR Class B EMI
IEC, EN Immunity
Standard features include:
Options and Accessories include:
11 watts per cubic inch
Integral ball bearing fan
DC Good signal
Inhibit capability
OVP on all models
Overload and short circuit protection
Reverse voltage protection
Redundancy via ultra low drop Or-ing
circuit with droop current share
Hi-Temp and Fan Fail signals
Nylon slides
1U high racking system
FEATURES
Fax: 215.699.2310
Model
LE1.8-56-YY
LE2.5-56-YY
LE3.3-56-YY
LE5-56-YY
LE12-25-YY
LE24-12.5-YY
LE48-6.3-YY
Model
LE12-33-YY
LE24-16.7-YY
LE48-8.3-YY
DESCRIPTION
The LE Series is part of Deltron’s SlimLine group of 1U high power
supplies. This series of single output self-cooled models is rated up to
400 watts, with each unit measuring 1.58”H x 2.10”W x 11.32”L.
Uniquely packaged and highly compact, LE Series modules fit a wide
range of industrial, telecom and computer networking applications.
These hot pluggable units can be paralleled for additional power or
used in combination with other models to meet multiple output
requirements. When used in Deltron’s RA30A racking system, as
many as six LE Series units can be mounted in a 1U high rack space,
providing up to 1800 watts.
Designed to meet applicable NEBS standards, units feature a proven
topology coupled with excellent thermal management to achieve
outstanding performance and safety. DC Good feature provides logic
signal for monitoring power supply status. All models are available with
redundancy option for parallel or N+1 hot pluggable applications. Low
voltage models include N channel ultra low drop Or-ing circuit to
maintain power supply efficiency.
LE SERIES RACK SYSTEM
The RA30A 1U high, 19”-wide racking system is available for
paralleling or N+1 redundant systems. The 1.75”-high by 12.0”-deep
rack can accommodate six LE Series power supplies, providing up to
1800 watts. Racks include a top cover for added strength and
protection.
Each power supply plugs into the backplane and is securely held in
place by removable front panels. Individual output and signal
connections are made via rear accessible Euro-style terminals and
headers. Two 3-terminal Euro-style input connectors are provided, one
for each half of the rack. Racks are designed to accept either EIA or
Bellcore NEBS mounting and heavy-duty solid-bearing slides.
OPTIONS
Option 04 is available for models with voltage ratings of 12 volts or greater.
Not available in combination with Option 08.
Option 08 is available for models with current ratings of 25 amps maximum.
Code
00
01
02
04
08
Function
None
Redundancy
Nylon slides
Hi-Temp and Fan Fail
Field Terminations
10 Models
1U Redundant Hot Swap Power Supplies
Single Output
LE SERIES
Up to 400 Watts

Related parts for le12-25-yy

le12-25-yy Summary of contents

Page 1

... Nylon slides 1U high racking system MODELS 300 Watt Output Model 1.8V @ 56A LE1.8-56-YY 2.5V @ 56A LE2.5-56-YY 3.3V @ 56A LE3.3-56- 56A LE5-56-YY 12V @ 25A LE12-25-YY 24V @ 12.5A LE24-12.5-YY 48V @ 6.3A LE48-6.3-YY 400 Watt Output Model 12V @ 33A LE12-33-YY 24V @ 16.7A LE24-16.7-YY 48V @ 8.3A LE48-8.3-YY Other ratings available on special order. ...

Page 2

LE SERIES SPECIFICATIONS INPUT 85-264 VAC, 47-63 Hz. For operation from 100 VAC to 85 VAC derate output current linearly to 85%. POWER FACTOR 0.99 typical. EMISSIONS EN 55022/CISPR 22, Class B Conducted. EN 61000-3-2, Harmonics. IMMUNITY EN 61000-4-2, Level ...