sc60021rm Staco Energy Products Co., sc60021rm Datasheet - Page 5

no-image

sc60021rm

Manufacturer Part Number
sc60021rm
Description
Parallel Redundancy/capacity On-line Ups
Manufacturer
Staco Energy Products Co.
Datasheet
worth taking care to install the system correctly and to have it maintained
correctly by your local dealer.
SAVE THESE INSTRUCTIONS - This Manual Contains Important Instructions
that should be Followed during Installation and Maintenance of the UPS and
Batteries.
Intended for Installation in a Controlled Environment.
CAUTION - A load disconnect switch shall be provided by others for the AC
output circuit. To reduce the risk of fire, connect only to a circuit provided
with branch circuit over-current protection for 30 amperes rating in
accordance with the National Electric Code, ANSI/NFPA 70.
CAUTION - To reduce the risk of fire, connect only to a circuit provided with
branch circuit over-current protection for 40 amperes rating in accordance
with the National Electric Code, ANSI/NFPA 70.
Use No. 10 AWG, 60C copper wire and 22.1 lb-in Torque force when
connecting to terminal block.
1.2.
For extended storage through moderate climate, the batteries should
be charged for 12 hours every 3 months by plugging the UPS power
cord into the wall receptacle and turn on input breaker on front panel.
Repeat this procedure every 2 months under high temperature
environment.
Storage Instruction
4