b110rlp System Sensor, b110rlp Datasheet - Page 2

no-image

b110rlp

Manufacturer Part Number
b110rlp
Description
Low-profile Plug-in Smoke Detector
Manufacturer
System Sensor
Datasheet
Engineering Specifications
The ionization detector model shall be equipped with a
dual-chamber, unipolar sensing chamber. The nominal sensi-
tivity of the detector shall be 1.0%/ft. as measured in a UL
smoke box and shall not alarm when it is exposed to wind
gusts up to 500 feet per minute. The photoelectronic detec-
tor model shall have a nominal sensitivity of 3.0%/ft. as
measured in a UL smoke box with a nominal signal-to-noise
ratio of 2.0. Both ionization and photoelectronic detector
models shall be available. The detector shall be equipped
with a light-emitting diode (LED) that is visible from the
floor. This LED shall blink every ten seconds to indicate that
the detector is operational, in standby, and latch on as a
visual indication of alarm. The detector shall be capable of
applying an output voltage to an optional remote LED
annunciator as an indication of its status. The photoelec-
tronic detector shall include built-in circuitry that performs
Specifications
Operating Voltage/Alarm Current
See Adapter Base Selection Guide following
Standby Current
Ion:
Photo:
Sensitivity
.97 ±.47%/ft. Ion; 3% ±.7%/ft. Photo
Shipping Weight
3.6 oz. (102 g)
Size
1.66 h. (42 mm)
4.1 /104 mm dia. unflanged base
6.1 /155 mm dia. flanged base
Adapter Base Selection Guide
Base Model Number
B110LP
B110RLP
B112LP
B114LP
B116LP
B401†
*Functionality contingent on panel compatibility
Relay Contact Ratings: Resistive or Inductive (60% power factor) load.
Form A:
Form C:
Junction Box Selection Guide*
Base Model Number
B401
B110LP/RLP
B112LP/B116LP
B114LP
*Box depth contingent on base and wire size. Refer to National Electrical Code or local applicable codes for appropriate recommendations.
40µA Standby
85µA Standby
2.0A at 30 VAC/DC
0.6A at 110VDC, 2.0A at 30VDC
1.0A at 125VAC, 2.0A at 30VAC
Single Gang
NO
YES
YES
NO
Loop Type
2-wire*
2-wire*
4-wire
4-wire
2-wire*
2-wire*
Current Limit Resistor
No
Yes
Yes
Yes
No
No
3
NO
YES
YES
NO
**Must be limited by control panel
1
2
Octagon
4 Octagon
NO
YES
YES
YES
Contact Type
Form A&C
Form A&C + A Super visor y
Form C
†Flangeless base
a functional test of all detection circuits at least once every
40 seconds without the need for generating smoke. It shall
be possible to perform a calibrated sensitivity and perform-
ance test on the detector without the need for generating
smoke. The test method shall test all detector circuits. The
detector screen and cover assembly shall be easily removable
for cleaning or replacement. It shall maintain stable opera-
tion when it is exposed to wind gusts of up to 3000 feet per
minute. The detector shall use a plug-in, low-profile design
that is both unobtrusive and aesthetically pleasing. A line of
plug-in bases for a variety of applications shall be available
for use with the detectors. Wire connections shall be made
by means of a clamping plate and screw. These bases shall
allow for mounting directly to a surface or to a 3
octagon box.
Construction
Flame retardant thermoplastic
Temperature
32°F to 120°F (0° to 49°C)
UL Listed Velocity Range
Ion:
Photo:
Humidity Range
10% – 93% RH noncondensing
Smoke Detector Spacing
On smooth ceilings (as defined in NFPA 72), spacing of 30 feet (900 sq. ft.)
may be used as a guide. Other spacing may be used depending on ceiling
height, high air movements, and other conditions or response requirements.
4 Square
NO
YES
YES
YES
0 – 500 fpm (0 – 2.5 m/s)
0 – 3000 fpm (0 – 15.2 m/s)
50 mm
YES
NO
YES
NO
Nominal Voltage
12/24VDC
24VDC
24VDC
120VAC
24VDC
12/24VDC
60 mm
YES
NO
YES
NO
Current Draw on Alarm (mA)
10–100**
22–62
14–39
75 mA AC Max
12–100**
10–100**
75 mm
NO
NO
YES
NO
1
2
or 4