CAB6-250-VL N/A, CAB6-250-VL Datasheet - Page 5

no-image

CAB6-250-VL

Manufacturer Part Number
CAB6-250-VL
Description
DELTA LOOP WIRING LINKS (SET 3
Manufacturer
N/A
Datasheet
Bulletin 100-M, 100-C, 104-C, 100S-C, 104S-C, CAB6, 100-G
Contactors
Overview - Bulletin 100-C, 100S-C
Compact design
Bulletin 100-C contactors switch more power and use less panel space. Despite
their small dimensions, they are powerful enough for use with the high starting
currents of today’s modern motors.
45 mm
45 mm
54 mm
72 mm
4
9 A, 12 A,
30 A,
43 A
60 A, 72 A,
16 A, 23 A
37 A
85 A
(AC-3 at 400/415 V)
Bulletin 100-C contactors for good connections
Two separate power connections per pole offer ease of wiring and high connection
reliability. The modern connection technology used by Bulletin 100-C contactors
saves both time and money.
Coil always positioned correctly
The dual connection technology always positions the coil connection for optimal
accessibility, whether below (on starters with circuit breakers), or above (on starters
using the revolutionary Bulletin 193-E Electronic Overload relay). Space- and cost-
saving coil modules (interface devices, protection elements, Electronic timers) can
always be added. When ordering, select the desired position of the coil connec-
tions. The position of the coil connections can also be adapted locally within sec-
onds, using simple tools.
Uniform accessories for the entire line of contactors
All Bulletin 100-C accessories can be used with all contactor sizes.The mechanical
interlock with integrated interlock contacts can be used alone to interlock the small-
est AC contactor with the largest.
Bulletin 100-C contactors for highest security
Bulletin 100-C contactors are rated for high personal protection and functional
security. The safety package consists of amongst other things
finger and back of hand accidental contact protection.
• Secure isolation of electric circuits
• Positively guided contacts
• Cover to prevent manual operation.
Comprehensive Safety for Operating Personnel and the Machine
The safety of both operators and machinery becomes more and more important.
Electrical controls can play an important contribution to safety. Various rules and
standards define the components and systems that are used in safety applications.
• Positively guided contacts according to IEC 947-5-1
• Fixed coupling of contactor and auxiliary contact block
• Protection against unintended actuation
• Auxiliary contacts that are electronically compatible according to DIN 19240
Positive Guidance of the Contacts
Positive guidance of contacts according to IEC 60947-5-1 is given when it
is ensured, that N.C. and N.O. contacts are never able to be closed at the same
time. Therefore a minimum opening distance of 0.5 mm is prescribed in the event
of failure. All contacts in the basic device are positively guided as well as the
normally closed contacts in the auxiliary contact block. The contacts in the basic
device as well as in the auxiliary contact blocks are guided restricted. The restricted
guidance also applies between basic device and accessories.
4-5
Rockwell Automation

Related parts for CAB6-250-VL