2251BR System Sensor, 2251BR Datasheet - Page 2

no-image

2251BR

Manufacturer Part Number
2251BR
Description
2251br Intelligent Photoelectric Smoke Sensor With Remote Test Capability In Duct Applications
Manufacturer
System Sensor
Datasheet
B.
When used properly, the canned smoke agent will cause the smoke detector
to go into alarm. Refer to the manufacturer’s published instructions for proper
use of the canned smoke agent.
Canned aerosol simulated smoke (canned smoke agent) formulas will vary by
manufacturer. Misuse or overuse of these products may have long term ad-
verse effects on the smoke detector. Consult the canned smoke agent manufac-
turer’s published instructions for any further warnings or caution statements.
C.
A sensor that fails any of these tests should be cleaned as described under
CLEANING, and retested. If the sensor fails after cleaning, it must be replaced.
When testing is complete, restore the system to normal operation and notify
the proper authorities that the system is back in operation.
fIgURE 3. TEST MAgNET POSITION:
System Sensor warrants its enclosed smoke detector to be free from defects in materials and workman-
ship under normal use and service for a period of three years from date of manufacture. System Sensor
makes no other express warranty for this smoke detector. No agent, representative, dealer, or employee
of the Company has the authority to increase or alter the obligations or limitations of this Warranty.
The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of
the smoke detector which is found to be defective in materials or workmanship under normal use and
service during the three year period commencing with the date of manufacture. After phoning System
Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective
units postage prepaid to: System Sensor, Returns Department, RA #__________, 3825 Ohio Avenue, St.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause Harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
SS-400-005
MANUfACTURER
Home Safeguard Industries
SDi
SDi
SDi
Two LEDs on the sensor are controlled by the panel to indicate sensor
status. Coded signals, transmitted from the panel, can cause the LEDs
to blink, latch on, or latch off. Refer to the control panel technical docu-
mentation for sensor LED status operation and expected delay to alarm.
Smoke Entry
The GEMINI model 501 aerosol generator can be used for smoke entry
testing. Set the generator to represent 4%/ft to 5%/ft obscuration as de-
scribed in the GEMINI 501 manual. Using the bowl shaped applicator,
apply aerosol until the panel alarms.
Additionally, canned aerosol simulated smoke (canned smoke agent)
may be used for smoke entry testing of the smoke detector. Tested and
approved aerosol smoke products are:
Remote Test
2251BR can be remotely tested using the RTS451, RTS451KEY, RTS151, or
RTS151KEY test accessories. Refer to the DNR/DNRW manual for wiring
diagrams. Maximum test response time may be up to two communica-
tions from the panel.
LED
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
Please refer to insert for the Limitations of Fire Alarm Systems
LED
CAUTION
TEST MAGNET
MAGNET TEST
POSITION
MODEL
25S
CHEK02 and CHEK06
SOLOA4
SMOKESABRE-01
MARKER
ThREE-yEAR LIMITED WARRANTy
C0145-02
fCC STATEMENT
2
CLEANINg
Before removing the detector, notify the proper authorities that the smoke
detector system is undergoing maintenance and will be temporarily out of
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.
fIgURE 4. SENSOR ASSEMBLy:
SPECIAL NOTE REgARDINg SMOkE DETECTOR gUARDS
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.
Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The
Company shall not be obligated to repair or replace units which are found to be defective because of
damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no
case shall the Company be liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s
negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential
damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific
legal rights, and you may also have other rights which vary from state to state.
Remove the sensor to be cleaned from the system.
Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place.
Vacuum the screen carefully without removing it. If further cleaning is
required continue with Step 4, otherwise skip to Step 7.
Remove the chamber cover/screen assembly by pulling it straight out.
Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber.
Reinstall the chamber cover/screen assembly by sliding the edge over the
sensing chamber. Turn until it is firmly in place.
Replace the cover using the LEDs to align the cover and then gently
pushing it until it locks into place.
Reinstall the detector.
Test the detector as described in TESTING.
COVER
REMOVAL
TABS
©2009 System Sensor
SENSOR
COVER
SENSING
CHAMBER
COVER AND
SCREEN
SENSING
CHAMBER
I56-3534-001R
C0215-03

Related parts for 2251BR