HVC319-FT Absopulse Electronics Ltd, HVC319-FT Datasheet

no-image

HVC319-FT

Manufacturer Part Number
HVC319-FT
Description
500w, Rugged, Ac/dc Industrial Power Supply With High Output Voltage Hvc 319-ft Series
Manufacturer
Absopulse Electronics Ltd
Datasheet
The HBC 319 Series heavy-duty, AC/DC industrial power supply uses a field-proven design to deliver 500W output power. It is a
mature design with a track record in numerous applications. Cooling is by conduction via baseplate to a heatsinking surface and
by natural convection. The unit features full electronic protection and low output noise. Low component count, large design
headrooms, and the use of components with established reliability result in a high MTBF. Additional ruggedizing and conformal
coating are available for operation in extreme environments. An optional built-in redundancy diode allows for parallel and N+1
operation. The unit is manufactured at our plant under strict quality control. Customized versions and fan-cooled versions with
increased output power are also available.
Input Voltage
115/230VAC +/- 15%
47 - 63Hz
Voltage selection by internal jumper
Input Protection
Inrush current limiting
Varistors
Internal safety fuse
Lower voltage than the specified
minimum input will not damage
the unit
Isolation
2250VDC input to chassis
4300VDC input to output
8mm spacing
500VDC output to chassis
Standards
Designed to meet EN60950
and corresponding UL and CSA
standards
EMI
EN55022 Class A as a minimum
Switching Frequency
55KHz +/- 3KHz
Hold Up Time
Minimum 5ms at full load for
5% drop of output voltage at
nominal input
Binder Caption: AC/DC Rectifiers
Enhancements to these general specifications and customizing can be accommodated upon request. Specifications are subject to change.
Rugged industrial quality
Single regulated and adjustable output
Convection cooling
Full electronic protection
Field-proven design
N+1 redundancy available
500W, Rugged, AC/DC Industrial Power Supply with High Output Voltage
Designer and manufacturer of quality converters, inverters, UPS systems, complete rack mount systems
and DC-input fluorescent lamp inverters since 1982. Custom or standard.
Output Voltages
125VDC/4A or 250VDC/2A are
standard
Consult factory for other voltages
Redundancy Diode
Available as option
Line/Load Regulation
± 1% combined from no load
to full load
Dynamic Response
Max 5% voltage deviation for
10% to 50% load step, with
better than 1msec recovery time
Output Ripple/Noise
Less than 1% of output voltage
peak to peak or 0.2% RMS of the
output voltage (20MHZ BW)
Output Overload Protection
Rectangular current limiting with
short-circuit protection (no hiccup)
Thermal shutdown in case of
insufficient cooling (self resetting)
Output Overvoltage Protection
Double regulator loop completely
stable and independent of main
loop
Absopulse is a BABT-approved Facility
HVC 319-FT Series
SPECIFICATIONS
July 7, 2009/TS/CL
Efficiency
Output voltage dependent.
Typically 80% at full load
Operating Temperature
0 to+50ºC for full specification,
Extended temp. range available
Temperature Drift
0.03% per
temperature range
Cooling
Conduction to customer heatsink
or chassis and natural convection
Environmental Protection
Basic ruggedizing
Full ruggedizing and conformal
coating as option
Humidity
5 – 95% non-condensing
MTBF
160,000 hours @ 45
Demonstrated MTBF is
significantly higher
Indicators
None on standard version
o
C over operating
o
C
ABOPULSE ELECTRONICS LTD
110 Walgreen Road
Ottawa, Ontario. K0A 1L0. CANADA
Tel: (613) 836-3511
E-mail:
www.absopulse.com
Made in Canada
Control Input
None
Alarm Output
None on standard version
Available as option
Package/Dimensions (WxHxL)
F4: 130 x 62 x 353 mm
(5.1 x 2.43" x 13.9) including
terminals and mounting flanges
Weight
2.2 kg (4.9 lb)
Connections
12 pole barrier type terminal block
with 3/8” spacing
RoHS Compliance
Fully compliant
Warranty
Two years subject to application
within good engineering practice
absopulse@absopulse.com
Fax: (613) 836-7488

Related parts for HVC319-FT