G3JA-C Omron Corporation, G3JA-C Datasheet

no-image

G3JA-C

Manufacturer Part Number
G3JA-C
Description
Three-phase Hybrid Soft Starter Soft Start, Kick Start, Current Limit Start, Soft Stop
Manufacturer
Omron Corporation
Datasheet
Built-in Bypass Relay and Smooth Motor Starts/Stops
Achieved in a Compact Starter
• Advanced functions include soft start, kick start, and soft stop.
• Phase control using a thyristor limits current when the motor starts, and a
• Controls 3-phase, 3-wire motor or 3-phase, 6-wire motor.
• Built-in electronic thermal overload relay.
• Built-in fault diagnosis for overtemperature, phase reversal, phase loss/open
• cULus listed; complies with IEC standards.
• Mounts with screws or to DIN track.
• Built-in operation/fault indicator.
• Built-in auxiliary contact for fault indication.
• Built-in auxiliary contact to output operating status.
• An Optional Auxiliary Contact Block can be added to output operating status.
Characteristics
Note: Select either voltage control start or current limit start.
Applicable Motors
Three-phase, 3-wire Motor
(Line)
The G3JA-C can be
used for a 3-phase,
3-wire motor as
shown in the
following diagram.
(Star-delta wiring for
the motor is required
if a 3-phase, 6-wire
motor is used.)
Item
Applicable
motors
Functions
bypass relay minimizes power loss while the motor is running.
load, current imbalance, and shorted SCR.
Three-phase Hybrid Soft Starter
(Soft Start, Kick Start, Current Limit Start, Soft Stop)
G3JA-C
Refer to Safety Precautions on page 16.
Rated operating voltage (motor)
Rated operating current (motor)
Applicable motor capacity
IEC 60947-4-2, 230 VAC
Voltage control start (See note.)
Kick start
Current limit start (See note.)
Soft stop
Fault detection relay output (NO)
Auxiliary contact output (NO)
Optional Auxiliary Contact Block
output
Fault detection LED indicator
Overload protection
Phase reversal detection
Current imbalance detection
Motor
Three-phase, 6-wire Motor
(Delta)
A 3-phase, 6-
wire motor
(that supports
a star-delta
operation
start) can be
used. The
G3JA-C is
compact and
includes
functionality
for devices
that start
operation with
star-delta
(
Type
3-phase, 3-lead
motor
3 to 37 A
0.55 to 7.5 kW
) wiring.
200 to 480 VAC
50/60 Hz
3-phase, 6-lead
motor (star-delta
wiring)
3 to 64 A
0.55 to 18.5 kW
(±5%)
Motor
(±10%)
Model Number Structure
■ Model Number Legend
Soft Starter
1. Controller Type
2. Rated Operating Voltage of Main Circuit
3. Rated Operating Current of Main Circuit
4. Terminal Type
5. Control Voltage
Accessories
1. Option
2. Number of Contacts
1. Option
G3JA-C@@@@
G32J-@@
G32J-@
C: Soft start/stop
4: 200 to 480 VAC, 3 phase, 50/60 Hz
03: 3 A
09: 9 A
16: 16 A
B: Screw terminals (screw clamps)
AC100-240: 100 to 240 VAC 50/60 Hz
AC/DC24:
CA: Auxiliary Contact Block
10: 1 NO
20: 2 NO
CF64: Fan
TA10: Round Terminal Block Adapter
1 2
1
1 2 3 4 5
19: 19 A
25: 25 A
24 VAC 50/60 Hz, 24 VDC
01: 1 NC
11: 1 NO/1 NC
30: 30 A
37: 37 A
CSM_G3JA-C_DS_E_5_1
1

Related parts for G3JA-C

G3JA-C Summary of contents

Page 1

... Phase reversal detection Current imbalance detection Note: Select either voltage control start or current limit start. Applicable Motors Three-phase, 3-wire Motor Three-phase, 6-wire Motor (Line) (Delta) The G3JA-C can be A 3-phase, 6- used for a 3-phase, wire motor 3-wire motor as (that supports shown in the a star-delta following diagram ...

Page 2

... Production of a new version of the Soft Starter (version 2) with added functions was started in August 2008. The DIP switch settings of the new version are different from the previous version. For details, refer to Upgrades for Version 2 on page 13. When replacing G3JA-C (version 2) with G3JA-D, refer to “Three-phase, 6-wire Motors (Star-delta Wiring)” list above. ■ Accessories (Order Separately) ...

Page 3

... G3JA-C416/C419 100 G3JA-C425/C430/C437 Load current (A) Model G3JA-C403 G3JA-C409 G3JA-C416 G3JA-C419 G3JA-C425 G3JA-C430 G3JA-C437 Rated breaking current Rated breaking current cULus (UL 508) G3JA-C G3JA-C425 G3JA-C430 G3JA-C437 ...

Page 4

... Hz, 0.19-mm single amplitude 2 peak Hz, 0.075-mm single amplitude 2 ( (15 G) G3JA-C IEC (EN/IEC 60947-4-2) III (See note.) IEC (EN/IEC 60947-4- 2,000 VAC III (See note.) AC15 IEC (EN/IEC 60947-4-2) IEC (EN/IEC 60947-4-2) ...

Page 5

... Applicable Standards Safety standards UL 508 (Listing: File No. E64562), CSA 22.2 No. 14, EN/IEC 60947-4-2 cULus (UL 508) cULus (UL 508) --- --- 4 kV contact discharge and 8 kV air discharge --- --- --- G3JA-C IEC (EN/IEC 60947-4-2) IEC (EN/IEC 60947-4-2) Class A Class A Conforms to IEC 60947-4-2 Conforms to IEC 60947-4-2 Conforms to IEC 60947-4-2 5 ...

Page 6

... G3JA. A transformer is not required if the load voltage is within the rated operational voltage range of the G3JA. *2. The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta G3JA (V1) (W1) (U2) G3JA-C Fuse, NF breaker, etc -TC Transformer * GRD ...

Page 7

... G3JA. A transformer is not required if the load voltage is within the rated operational voltage range of the G3JA. *2. The wiring in the following diagram is used for a 3-phase, 6-wire motor (Delta G3JA (U2 (V1) (W1) G3JA-C Fuse, NF breaker, etc Transformer *2 - -KM2 GRD -SB E-STOP ...

Page 8

... If the motor load is extremely small, the soft stop time will be very short. G3JA-C Kick start (when selected) *2 100% Stable ...

Page 9

... LED indicator and closes the alarm contact. Shorted SCR The G3JA-C always checks the SCR for a short circuit before the starting sequence short circuit is found, the G3JA-C stops the starting sequence, indicates the short circuit with a flashing LED indicator, and closes the alarm contact ...

Page 10

... Note: Test Mode for overload testing will be entered when the Reset Button is pressed for approximately seconds. Test Mode will be cancelled when the Reset Button is pressed again. Control Terminals The G3JA-C has eight input terminals on the front. Each terminal is described in the following table. Description Terminal A1 ...

Page 11

... Normal Up-to-speed Soft stop Coast to stop during soft stop Start Stop Stable operation Time Normal Up-to-speed Normal: Power supplied to motor Up-to-speed: Bypass relay ON G3JA-C Current Limit Start Setting DIP switch pins FLA current limit (%) 4 5 OFF OFF 150% ON OFF 250% OFF ...

Page 12

... Mounting Dimensions for the Auxiliary Contact Block and Round Terminal Block Adapter Trip Class 15 1,000 Cold trip 100 Hot trip 10 1 100 1,000 Current (%) 44.8 109 141.5 10 44.8 109 23 141.5 23 G3JA-C Trip Class 20 1,000 Cold trip 100 Hot trip 10 1 100 1,000 Current (%) (Unit: mm) Panel Cutouts 4.5 dia 46.4 132 35 3 46.4 ...

Page 13

... Optional Auxiliary Contact Block (normal/up-to- speed) 16 Phase reversal protection * These settings are different for the previous version and the new version. G3JA-C Label on Box Previous version New version (version 2) Start time Start mode (current limit start or soft start) ...

Page 14

... Motor Wiring Method (New Version) Optional Auxiliary Contact Block (Previous Version) Previous version DIP switch pin 15 Optional Auxiliary Contact Block ON (23 to 24) Normal OFF Up-to-speed G3JA-C New version (version 2) DIP switch pins Time (unit OFF OFF OFF OFF ON OFF 10 ON ...

Page 15

... Tighten the screws to the specified torque. The tightening torque for mounting the Round Terminal Block Adaptor to the G3JA is 2.3 to 3.4 N·m. The tightening torque for wiring the Round Terminal Block Adaptor is G3JA is 0.98 to 1.37 N·m. G3JA-C Fan Three, M4 ...

Page 16

... Varistor voltage: 910 V Energy resistance: 200 joules min. (10 × 1000 µs) Limiting Resistor The G3JA cannot use a limiting resistor. Operation Start Signal Do not apply an operation start signal during a soft stop. Doing so will result in abnormal operation. G3JA Motor T3 ...

Page 17

... If you use a power capacitor, connect it to the primary side (i.e., power supply side) of the G3JA output terminals. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527. In the interest of product improvement, specifications are subject to change without notice. G3JA-C 17 ...

Page 18

... OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ Read and Understand This Catalog Warranty and Limitations of Liability Application Considerations Disclaimers In the interest of product improvement, specifications are subject to change without notice. (c)Copyright OMRON Corporation 2009 All Right Reserved. 2009.12 ...

Related keywords