MAX7358 Maxim, MAX7358 Datasheet - Page 11

no-image

MAX7358

Manufacturer Part Number
MAX7358
Description
The MAX7356/MAX7357/MAX7358 8-channel I²C switches/multiplexers expand the main I²C bus to any combination of 8 extended I²C buses
Manufacturer
Maxim
Datasheet

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
MAX7358EUG
Manufacturer:
MAXIM/美信
Quantity:
20 000
Part Number:
MAX7358EUG+
Manufacturer:
Maxim
Quantity:
526
If either line of any downstream bus is low for a period
exceeding 25ms between t
MAX7357/MAX7358 detect a lock-up fault on that bus
and takes the action configured by the user. If the lock-
up is not on the main bus, SDA and SCL return to the
high state at the same time. The MAX7357 or MAX7358
then identifies which SD_ or SC_ is still pulled low. If the
optional interrupt function is enabled (by setting B0 of
the configuration register), an active-low interrupt is
generated at RST/INT.
If B4 in the configuration register is set to 1, then only
faults on connected buses cause the MAX7357 or
MAX7358 to disconnect all buses from each other.
When this is the case, faults detected on disconnected
buses set the flag in the lock-up status register, and, if
enabled, notify the host of the fault, but do not discon-
nect the buses from one another.
B1 of the configuration register enables the flush-out
sequence. If this bit is set to 1, the MAX7357 or
MAX7358 attempts to send a flush-out sequence over
the locked SD_ and SC_ pair (the sequence begins at
t
the locked bus (SD_ and SC_) is released at t
6). The I
MAX7357 or MAX7358 lock-up status register to iden-
tify the locked-up bus. If RST/INT is enabled as an
interrupt, it is released once a read command to the
lock-up indication register is received by the MAX7357
or MAX7358 (shown at t
can also be automatically released after a 1.6s delay
by setting bit 2 of the configuration register.
Figure 6. Bus Lock-Up Detection, Isolation, and Notification Timing Diagram
5
in Figure 6). If the flush-out sequence is successful,
1-to-8 I
RST/INT
Lock-Up Detection, Isolation, and Notification
SDA
SD_
SC_
SCL
2
C master (at SDA and SCL) reads the
Bus Lock-Up Detection, Isolation,
______________________________________________________________________________________
t
and Notification Operation
2
1
C Bus Switches/Multiplexers with Bus
7
in Figure 6). The RST/INT
(MAX7357/MAX7358)
1
t
2
NOTE: THE FLUSH-OUT SEQUENCE RUNS AT AN SC_ FREQUENCY OF 40kHz.
THE HOST MAY COMMUNICATE AT UP TO 400kHz. THE TIMING SHOWN IS NOT TO SCALE.
and t
t
3
t
4
t
5
2
SDA Stuck Low
in Figure 6, the
6
(Figure
t
6
By setting bit B7 in the configuration register to 1, a pre-
connection wiggle test is enabled for all downstream
buses. This test only runs on the downstream bus when
the bus is selected through the switch control register.
Enabling this test does not affect any bus that is already
connected to the host bus; however, deselecting and
subsequently reselecting the bus will cause the test to
occur. The test is performed when the switch control reg-
ister bit (or bits if multiple buses are selected in the same
I
is received. It consists of the MAX7357 or MAX7358
pulling the downstream clock line low, then the down-
stream data line low. Both lines are checked for a nomi-
nal low value, and then the clock line is released followed
by the data line (Note: This is an I
is seen by any I
bus). If either the clock or data line (or both) fail to pull
low during the test, the MAX7357 or MAX7358 do not
allow that downstream bus to connect to the host. If the
optional interrupt notification bit is set (B0), the device
notifies the host that a fault has occurred. The I
can then read the MAX7357 or MAX7358 registers to find
out which bus or buses caused the fault. Faults detected
by this test are stored in the preconnection fault register
(0x06). The stuck high Fault register is cleared once this
register is read, resetting the device, or disabling the
preconnection test.
The MAX7356/MAX7357/MAX7358 family of devices
has selectable device addresses through three external
inputs. The slave address consists of 4 fixed bits
(A6–A3 set to 1110); followed by 3 pin-programmable
bits (A2, A1, A0), as shown in Figure 7. The addresses
A2, A1, and A0 can also be driven dynamically if
required, but the values must be stable when they are
expected in the address sequence.
FLUSH-OUT DATA
2
C transaction) toggles from 0 to 1 and a stop condition
BYTE1
2
C devices connected to the extended
Preconnection Wiggle Test
(MAX7357/MAX7358)
(Stuck High Fault)
2
C stop condition and
BYTE4
Device Address
2
C master
t
7
11

Related parts for MAX7358