PU600 Powerbox, PU600 Datasheet

no-image

PU600

Manufacturer Part Number
PU600
Description
Manufacturer
Powerbox
Datasheet

Available stocks

Company
Part Number
Manufacturer
Quantity
Price
Part Number:
PU600-A15
Manufacturer:
MATSUSHITA
Quantity:
57
Part Number:
PU600-A15
Manufacturer:
ACBLE
Quantity:
530
PU600-PU1000
4 8 0 - 1 0 0 0 W A T T S D C / D C S I N G L E
Specifications
INPUT
Input voltages
Max accepted input ripple
50–400Hz
Input power at no load, max 15W
Reverse input voltage
protection
Input code B, 24, 48, 72
Input code C, D, 110, 220
Inrush current limit
Isolation
Input/case
Input/output
Output/case
OUTPUT
Output Voltages
Source regulation
Load regulation
(0-100% load) master
Transient recovery time for
10%/90%
Typ output ripple (60kHz) mV
pk-pk2
Input ripple attenuation on
Output (50–400Hz)
Temperature coefficient
Output adjustment range
with 15 Turn potentiometer
Current limit, rectangular
Remote sense
Soft start
Startup time
Holdup time
Features
Convection cooled
High efficiency
Current sharing
Overvoltage protection OVP
Over/under voltage alarm
Operating temperature range -25°C to 55°C
Reverse input voltage protection
PU600: 20-60Vdc(B), 50-150Vdc(C), 90-
270Vdc(D).
PU1000: 18-32Vdc(24), 38-60Vdc(48), 50-
90Vdc(72), 88-150Vdc(110), 175-300Vdc(220).
2% of nom. voltage
Yes
Parallel diode
Series diode
Input Code B, 24,48, 72 No
Input Code C, D, 110, 220 Yes, <6 x Inom.
Input Code B, 24, 48, 72 2kVDC
Input Code C, D, 110, 220 2.5kVDC
<75Vdc 2KVdc, >75Vdc 4KVdc
12–110V
0.1%
0.3%
<3mS. Load step, to within 3% of nominal
output voltage
30mV
150:1
0.02% per °C
95%–110%
105%
Yes
Yes.
1 Sec
2-25mS. Contact Powerbox
Your dependable power partner – www.powerbox.com.au
OPERATING
Design topology
Switching frequency
Efficiency
Overvoltage protection
Reverse Input Voltage
Protection
STANDARDS AND APPROVALS
Safety standards
C-Tick
EMC standards
ENVIRONMENTAL
Operating Temperate
Conduction Cooling
Storage Temperature Range -40°C to +85°C
MECHANICAL
Dimensions (HxWxD)
Weight
PU600/1000
Mounting brackets
Push-Pull
30kHz
85%–92%
Yes, 115% of nominal voltage.
Yes. input code B, 24, 48 with a parallel diode,
other input use a input series thyristor.
IEC60950, Low Voltage Directive.
AS/NZS CISPR11 Group 1, Class A
EN55011-B, EN55022-B, IEC61000-6-2, IEC61000-
4-2, -3, -4, -5, -6, -8,-10, EN50155 Figure 4.
-25°C to +55°C at 100% load
With derating, +70°C
86x420x337mm
10kg
Supplied with L89-1 mounting brackets
Please consult Powerbox for mounting options
137

Related parts for PU600

PU600 Summary of contents

Page 1

... Over/under voltage alarm • Operating temperature range -25°C to 55°C • Reverse input voltage protection Specifications INPUT Input voltages PU600: 20-60Vdc(B), 50-150Vdc(C), 90- 270Vdc(D). PU1000: 18-32Vdc(24), 38-60Vdc(48), 50- 90Vdc(72), 88-150Vdc(110), 175-300Vdc(220). Max accepted input ripple 2% of nom. voltage 50–400Hz Input power at no load, max 15W ...

Page 2

... PU600B15 20-60V 15V 40A 600W PU600B24 20-60V 24V 25A 600W PU600B48 20-60V 48V 12.5A 600W PU600C12 50-150V 12V 40A 480W PU600C13.8 50-150V 13.8V 40A 552W PU600C15 50-150V 15V 40A 600W PU600C24 50-150V 24V 25A 600W PU600C48 50-150V 48V 12.5A 600W PU600D12 90-270V 12V ...