Ordering Guide Mini 1U Power System ~ 2054136 R2, October 2008
System Parameters
Runaway
Temperature
Runaway Stop
Voltage
LVD Settings
Disconnect Voltage
Disconnect Delay
Reconnect Voltage
Reconnect Delay
Line Cord Naming Convention
Use the following naming convention to identify appropriate AC cables:
L D 10 08 – L 650P
The temperature at which the
controller will activate thermal
runaway
The voltage to which the rectifiers
will reduce for temperatures
above Runaway Temperature
The system LVD contactor will
open if the battery voltage falls
below this setpoint.
The amount of time (HH:MM:SS)
that the plant voltage must be
below the LVD disconnect setpoint
prior to disconnecting the LVD
contactor.
The system LVD contactor will
reconnect if the battery voltage
exceeds this setpoint.
The amount of time (HH:MM:SS)
that the plant voltage must
exceed the LVD reconnect
setpoint prior to reconnecting the
LVD contactor.
Table 6 – NIC Controller Parameters (Profile A01)
Figure 5 – Line Cord Naming Convention
Description
Line Cord Series
Shelf Connection
Cord Length
Conductor Size
AC Plug Retention
NEMA AC Plug Type (NEMA code or,
11.5 Vdc
Nominal
0:00:05
0:00:20
9.5 Vdc
12 Volt
11 Vdc
60 °C
(L is always first character)
(L=ring terminals, I=IEC
(feet)
(AWG)
(L=Locking, N=Non-locking,
U=Un-terminated)
U=Un-terminated)
D=two hole lug, U=Un-Terminated)
Nominal
0:00:05
0:00:20
24 Volt
25 Vdc
21 Vdc
25 Vdc
60 °C
Nominal
0:00:05
0:00:20
48 Volt
50 Vdc
42 Vdc
50 Vdc
60 °C
11